2019-07-03 08:36:57 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY MECHANICAL |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND |
| SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN |
| AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT |
| CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. |
| |
| 2) FBC-R - M1305.1.3 APPLIANCES IN ATTICS. |
| ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN |
| OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE |
| ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT |
| NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES |
| (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG |
| MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM |
| THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE |
| CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 |
| NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE |
| SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES |
| (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE |
| APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS |
| OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY |
| 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW |
| REMOVAL OF THE LARGEST APPLIANCE. |
| |
| 3) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS. |
| A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE |
| REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| ACCORDANCE WITH CHAPTER 34. |
| |
| 4) THE SECOND FLOOR MECHANICAL PLAN SHOWS A 15" WIDE |
| DUCT CHASE FOR THE RETURN AND SUPPLY AIR FOR THE FIRST |
| FLOOR. THE RETURN DUCT FROM THE FIRST FLOOR IS SHOWN AS |
| 18". THE CHASE IS TOO SMALL TO ACCOMADATE THE 18" DUCT. |
| FBC 107.2.1 |
| |
| |