2019-03-06 10:53:51 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET |
| OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE |
| SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE |
| DESIGN. A DIGITAL SIGNATURE ON A PAPER PLAN IS NOT |
| ACCEPTABLE. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; |
| FS 471, 481 |
| 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| RE E3606.3 |
| 3. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3, |
| 110.9; FBC RE E3606.3 |
| 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| FBC EC C405.1, R404.1 |
| 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| 6. PROVIDE LOCATION OF ELECTRICAL SERVICE AND |
| ELECTRICAL PANEL ON PLAN TO CONFIRM CODE COMPLIANCE. |
| WPB FBC 107.2.1 |
| 7. PLAN DOES NOT SHOW THE SMOKE ALARM REQUIRED ON FIRST |
| FLOOR. PROVIDE CORRECTION TO CONFIRM CODE COMPLIANCE. |
| FBC RE R314.3; WPB FBC 107.2.1 |
| 8. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION FOR |
| BATH 2. NEC 410.10(D); FBC RE E4003.11 |
| 9. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS |
| LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY |
| ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS |
| SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE |
| CORRECTION. NEC 410.16; FBC RE E4003.12 |
| 10. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| PROVIDE CORRECTION FOR MASTER BATH AND POWDER BATH. NEC |
| 210.11(C)(3), 210.52(D); FBC RE E3703.4, E3901.6 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |