2019-09-16 11:14:54 | 1) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 |
| FBC-R SEC. G2413.4.1, G2413.4.2. THE FLAT DRAWING THAT |
| HAS BEEN SUBMITTED IS UNACCEPTABLE AS IT IS EXTREMELY |
| DIFFICULT TO TELL WHERE THE LINES START AND END. |
| SEC.107.3.5.3 OF WPB AMEND. TO FBC. 2ND REQUEST. |
| 2.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| G2413.4 (1 ) THROUGH G2413.4 (21). 2ND REQUEST |
| 3.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| SEC. G 2413.4.1, G2413.4.2.2ND REQUEST. |
| 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| THE GAS PLAN NOTES 5 PSI AND 1/2 LB. CLARIFY.2ND |
| REQUEST. |
| 5) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| THE ONLY GAS APPLIANCE ON THIS SYSTEM. IF NOT, SUBMIT A |
| COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF |
| PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, |
| THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, |
| THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. |
| 6) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN |
| SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND |
| THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION |
| OF THE WATER HEATER SHALL COMPLY WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC |
| SEC. 107.2.1. 2ND REQUEST. THE FLOOR PLAN THAT WAS |
| SUBMITTED NEEDS TO BE REDONE SO THAT IT CLEARLY |
| REFLECTS THE LOCATION OF THE TANKLESS WATER HEATER.2ND |
| REQUEST. |
| 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3.2ND REQUEST. |
| 8) THE PLANS INDICATE AN EXISTING GAS METER/LP TANK AND |
| CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS |
| ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST |
| BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO |
| ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF |
| UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.2ND REQUEST. |
| 9) SUBMIT ONE ADDITIONAL COPY OF THE INSTALLATION |
| MANUAL. WPB AMEND. TO FBC SEC. 107.2.1. |
| 10) INDICATE ON THE MANUFACTURER'S SPECIFICATIONS WHICH |
| MODEL OF THE WATER HEATER IS BEING INSTALLED. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 11) PLACE A NOTE ON THE PLAN HOW THE WINDOW IS |
| NON-OPERATIONAL. SCREWING THE WINDOW SHUT IS NOT |
| ACCEPTABLE. IF THIS IS A FIXED WINDOW, THEN NOTE SUCH |
| ON THE PLANS. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |