2019-04-01 07:46:03GAS 1ST REVIEW***DENIED** NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
  
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2
  
 2) ANSWERED*****SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3) TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.\
  
 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3. YOU SUBMITTED 37 DIFFERENT
 SIZING CHARTS. WHICH ONE?
  
 5) PAGE 21 CALLS OUT 4' MIN FOR A NON DIRECT VENT UNIT.
 YOU PLAN CALLS OUT FOR 28". PROVIDE A PLAN WITH A NEW
 LOCATION.SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1
  
 6) ANSWERED****** INDICATE ON THE PLAN IF THE TANKLESS
 WATER HEATER IS THE ONLY GAS APPLIANCE ON THIS SYSTEM?
 IF NOT, SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE
 SIZES, TYPE OF PIPE, THE DEVELOPED LENGTH TO THE
 FURTHEST GAS OUTLET, THE BTU LOAD OF EACH APPLIANCE,
 THE PSI OF THE SYSTEM, THE TYPE OF GAS AND THE TOTAL
 BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS ALSO APPLY
 TO A NEW GAS SYSTEM. NOTE CITY RECORDS SHOW OTHER GAS
 APPLIANCES. LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21).
  
 7) PROVIDE WHICH OF THE 3 DIFFERENT MODELS ON THE
 INSTALLATION MANUAL YOU ARE USING.STATE WHICH
 MODELTANKLESS YOU PLAN TO INSTALLED. SUBMIT FULL
 MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED.
  
 8) ANSWERED******SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2
  
 9) NEW COMMENT: PLANS/ DOCUMENTS SHALL BE DRAWN UPON
 SUITABLE MATERIAL. PENCIAL IS NOT PERMITTED. FBC
 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703
  
  
  