2019-04-01 07:46:03 | GAS 1ST REVIEW***DENIED** NOTE - A COMPREHENSIVE REVIEW |
| COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN |
| REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| |
| |
| 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| G2413.4.1, G2413.4.2 |
| |
| 2) ANSWERED*****SHOW THE TYPE OF PIPE MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD |
| NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING |
| (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| FBC SEC.107.2.1. |
| |
| 3) TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC. |
| 107.2.1.\ |
| |
| 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. YOU SUBMITTED 37 DIFFERENT |
| SIZING CHARTS. WHICH ONE? |
| |
| 5) PAGE 21 CALLS OUT 4' MIN FOR A NON DIRECT VENT UNIT. |
| YOU PLAN CALLS OUT FOR 28". PROVIDE A PLAN WITH A NEW |
| LOCATION.SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMEND. TO FBC SEC. 107.2.1 |
| |
| 6) ANSWERED****** INDICATE ON THE PLAN IF THE TANKLESS |
| WATER HEATER IS THE ONLY GAS APPLIANCE ON THIS SYSTEM? |
| IF NOT, SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE |
| SIZES, TYPE OF PIPE, THE DEVELOPED LENGTH TO THE |
| FURTHEST GAS OUTLET, THE BTU LOAD OF EACH APPLIANCE, |
| THE PSI OF THE SYSTEM, THE TYPE OF GAS AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS ALSO APPLY |
| TO A NEW GAS SYSTEM. NOTE CITY RECORDS SHOW OTHER GAS |
| APPLIANCES. LIST THE BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 |
| FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 |
| AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). |
| |
| 7) PROVIDE WHICH OF THE 3 DIFFERENT MODELS ON THE |
| INSTALLATION MANUAL YOU ARE USING.STATE WHICH |
| MODELTANKLESS YOU PLAN TO INSTALLED. SUBMIT FULL |
| MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION |
| MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE |
| SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3. |
| GAS APPLIANCES SHALL BE LISTED AND LABELED. |
| |
| 8) ANSWERED******SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE |
| MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER |
| THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 |
| FBC-RES. SEC. G 2413.4.1, G2413.4.2 |
| |
| 9) NEW COMMENT: PLANS/ DOCUMENTS SHALL BE DRAWN UPON |
| SUITABLE MATERIAL. PENCIAL IS NOT PERMITTED. FBC |
| 107.2.1 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| 561-248-2703 |
| |
| |
| |