Date |
Text |
2019-02-24 13:54:36 | 1) THE DESCRIPTION OF WORK ON THE APPLICATION |
| STATES"EXACT CHANGE OUT FOR BATHROOM". EXACT CHANGEOUT |
| OF WHAT? THE PLANS ARE SO VAGUE A COMPREHENSIVE REVIEW |
| COULD NOT BE PERFORMED. CLEARLY INDICATE ON THE PLANS |
| AND THE PERMIT APPLICATION THE ENTIRE SCOPE OF WORK TO |
| BE PERFORMED. WPB AMEND. TO FBC SEC. 107.2.1. |
| 2) SUBMIT TWO COPIES OF AN EXISTING FLOOR PLAN SHOWING |
| THE PRESENT LAYOUT AND PLUMBING FIXTURES. WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 3) INDICATE ON THE PLANS IF ANY NEW FLOORING IS BEING |
| INSTALLED. IF SO, SHOW THE TYPE OF FLOORING TO BE |
| INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1. |
| 4) IF NEW FLOORING IS TO BE INSTALLED, SUBMIT TWO |
| COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| UNDERLAYMENT MATERIAL.WPB AMEND. TO FBC SEC. 107.2.1. |
| THE UNDERLAYMENT SHALL MEET THE FOLLOWING CRITERIA: |
| |
| FBC-B 2017 SEC.1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492?09. |
| |
| 1B) FBC-B 2017 SEC.1207.2 - AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90-04. |
| |
| 2) FLAME SPREAD- FBC-B 2017 SEC. 603.1(2) EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| 2017 FBC SEC.720.2 - CONCEALED INSTALLATION. |
| INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 2017 FBC SEC.703.5 - NONCOMBUSTIBILITY TESTS. |
| THE TESTS INDICATED IN SECTIONS 703.5.1 AND 703.5.2 |
| SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| |
| 2017 FBC SEC. 703.5.1 ELEMENTARY MATERIALS. |
| MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| IN ACCORDANCE WITH ASTM E 136. |
| |
| 2017 FBC SEC. 703.5.2 COMPOSITE MATERIALS. |
| MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 SHALL BE ACCEPTABLE AS |
| NONCOMBUSTIBLE MATERIALS. |
| |
| 5) SUBMIT TWO COPIES OF THE NONCOMBUSTIBILITY TESTS FOR |
| REVIEW.WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 6) THIS WORK MUST BE DONE BY A LICENSED GENERAL |
| CONTRACTOR OR BUILDING CONTRACTOR. A RESIDENTIAL |
| CONTRACTOR CANNOT PERFORM THIS WORK PER FL. STATUTE |
| 489.105. SUBMIT A NEW APPLICATION FROM A GENERAL OR |
| BUILDING CONTRACTOR. |
| |
| 7) A SEPARATE PLUMBING PERMIT APPLICATION IS REQUIRED |
| BY A LICENSED PLUMBING CONTRACTOR FOR THE PLUMBING |
| WORK. |
| |
| NOTE: ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| AFTER CORRECTIONS ARE SUBMITTED. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |