2019-03-22 14:49:02BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ADDITIONAL COMMENTS:
  
 1. PROVIDE CONNECTION DETAIL FOR THE NEW 5 #10 REBAR TO
 THE EXISTING COLUMNS. FBC 107
  
 2. WE TOOK A LOOK TO THE ORIGINAL STRUCTURAL DRAWINGS.
 THE DRAWINGS ARE SHOWING THE EXISTING REBAR IN THE
 BEAMS IS 6 #11 BOTTOM. THE NEW CONSTRUCTION DETAIL
 SUBMITTED ON PAGE S9.0 SPECIFY 5 #10 REBAR. THE BEAM
 CAPACITY APPEARS TO BE REDUCE FROM THE ORIGINAL DESIGN.
 PLEASE SUBMIT THE ENGINEERED CALCULATIONS WITH ORIGINAL
 SIGNATURE TO THE BUILDING OFFICIAL FOR REVIEW. FBC 107
  
 3. PLEASE PROVIDE A PLAN WHERE SHOW THE PROPOSED
 SHORING LOCATION. FBC 107
  
 I CAN PROVIDE THE ORIGINAL CONSTRUCTION DRAWINGS VIA
 EMAIL IF NEED IT.
  