Plan Review Notes
Plan Review Notes For Permit 19020375
Permit Number 19020375
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-03-29 11:33:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET A 2.1 - THERE IS AN INDICATION OF FUTURE
 RACKING.
  
 ANY RACK INSTALLATION SHALL BE UNDER SEPARATE SHOP
 DRAWINGS TO INCLUDE, HEIGHT, RACK MANUFACTURER'S SPEC
 SHEETS, STORAGE COMMODITY TYPE, WRAPPINGS, PALLETS,
 SHELVING, FASTENER'S TO THE SLAB. AND A FIRE SPRINKLER
 PRTOTECTION REVIEW BY A CERTIFIED FIRE SPRINKLER
 CONTRACTOR OR LICENSED ENGINEER.
  
 RACK SPRINKLERS MAY BE REQUIRED.
  
  
  
 2) SHEET E 1 - NEW CEILING FANS INSTALLATIONS ARE
 INDICATED.
  
 NEW CEILING FANS SHALL NOT ONSTRUCT FIRE SPRINKLERS.
  
 PLEASE CONSULT A FIRE SPRINKLER CONTRACTOR PRIOR AND
 AFTER INSTALLTION TO ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  