2019-04-10 13:56:18 | ***CORRECTIONS*** |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 2ND BUILDING REVIEW DENIED: |
| |
| 1. FBC B 107.2.1 PLEASE CONFIRM STATUS OF FIRE |
| SPRINKLERS. |
| 2. OK |
| 3. OK |
| 4.A. FBC B 1609.1.2, & 1609.6.4.4.1 PLEASE SUBMIT THE |
| PRODUCT APPROVALS FOR WINDOWS AND PRE-ENGINEERED A/C |
| STANDS. |
| 4.B. WPB AMENDMENTS 107.3.4 WHEN SUBMITTING, PLEASE |
| PROVIDE REVIEW STAMP AND SIGNATURE BY THE DESIGNER OF |
| RECORD ON PRODUCT APPROVALS. |
| 5. FBC B 107.2.1 PLEASE PROVIDE WELDING INFORMATION (ON |
| PLAN) FOR THE ROOF TOP STAND TO THE ROOF FRAMING |
| MEMBERS; AND IN ADDITION TO THE REQUIRED WELDING |
| INFORMATION ON PLANS PLEASE PROVIDE A (PROVISO REQUIRED |
| AT TIME OF INSPECTION) WELD PROCEDURE SPECIFICATION AND |
| WELDER |
| PERFORMANCE QUALIFICATION RECORD AS PER AWS D1.1 CLAUSE |
| 3.1 AND 4.15. |
| 6. FBC B 107.2.1/FBC M 306.5 PLEASE SHOW DETAILS FOR |
| ROOF ACCESS, INCLUDING MATERIAL, CONNECTIONS, AND |
| LOCATIONS. |
| 7. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE |
| REVISION AND REMOVE ANY VOIDED SHEETS AND REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |