2019-03-12 18:22:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020375
 3/12/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW OFFICE AC SYSTEM- SECTION C403.2.1 FBC EC.
  
 2) SUBMIT ENERGY CALCULATIONS FOR THE NEW CONDITIONED
 ENCLOSED SPACE- SECTION C503.2 FBC EC. REFER TO SECTION
 C402.2.2: INSULATION INSTALLED ON THE SUSPENDED CEILING
 SHALL BNOT BE CONSIDERED PART OF THE MINIMUM THERMAL
 RESISTANCE OF THE ROOF INSULATION.
  
 3) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR THE ROOF STAND AND LOUVER.
  
 4) M-1: PROVIDE AN AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPER FOR THE O/A INTAKE DUCT- SECTION C403.2.4.3
 FBC-17 EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  