2019-02-20 13:49:10 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) SHEET A 2.1 - THERE IS AN INDICATION OF FUTURE | | RACKING. | | | | ANY RACK INSTALLATION SHALL BE UNDER SEPARATE SHOP | | DRAWINGS TO INCLUDE, HEIGHT, RACK MANUFACTURER'S SPEC | | SHEETS, STORAGE COMMODITY TYPE, WRAPPINGS, PALLETS, | | SHELVING, FASTENER'S TO THE SLAB. AND A FIRE SPRINKLER | | PRTOTECTION REVIEW BY A CERTIFIED FIRE SPRINKLER | | CONTRACTOR OR LICENSED ENGINEER. | | | | RACK SPRINKLERS MAY BE REQUIRED. | | | | | | | | 2) SHEET E 1 - NEW CEILING FANS INSTALLATIONS ARE | | INDICATED. | | | | NEW CEILING FANS SHALL NOT ONSTRUCT FIRE SPRINKLERS. | | | | PLEASE CONSULT A FIRE SPRINKLER CONTRACTOR PRIOR AND | | AFTER INSTALLTION TO ENSURE COMPLIANCE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|