2019-02-27 08:01:36 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19020375 |
| ADD: 5786 PREMIER PARK DR. |
| CONT: DUKE INDIANA CONSTRUCTION |
| TEL: 954-453-5660 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 27/ 2019 |
| ACTION: DENIED |
| |
| 1) THE ORIGINAL PERMIT FOR THIS TENANT SPACE 10040216 |
| AND THE APPLIED FOR PERMIT / PLANS INDICATE THAT THIS |
| IS A FIRE SPRINKLERED BUILDING. LESS THAN 50 HEADS A |
| FIRE SPRINKLER CONTRACTOR CAN DESIGN THE ADDITIONAL |
| HEADS IN AN EXISTING FIRE SPRINKLER SYSTEM. A |
| CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV, CERTIFIED |
| UNDER SECTION 633.521, FLORIDA STATUTE MAY DESIGN A |
| FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY |
| DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER |
| SYSTEM. |
| |
| 2) NOTICE: SHEET A2.1 DOES INDICATE THERE WILL BE |
| FUTURE RACK STORAGE UNDER A SEPARATE PERMIT. NOTING |
| THAT RACK STORAGE IS NOT PART OF THIS PERMIT. |
| |
| 3) SHEET A-2 DOES INDICATE THE EXTERIOR CONCRETE WALL |
| WILL BE CUT AND SEE SHEET S-1. PLEASE ALSO REVIEW SHEET |
| M-1, THE PLAN SHOWS A SECOND 12 X 12 INCH PENETRATION |
| OF THE EXTERIOR WALL FOR INTAKE OF OUTSIDE AIR. SHEET |
| S-1 DOES NOT INDICATE THE 2ND PENETRATION AND WILL NEED |
| TO UPDATE THE PLANS. 107.2.1.2 ADDITIONAL INFORMATION |
| IS REQUIRED. PLEASE ALSO INCLUDE THE PRESSURES FOR THE |
| INTAKE LOUVER. |
| |
| 4A) PLEASE PROVIDE COMPLIANCE WITH: 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(B) WINDOWS |
| (C) WALL LOUVERS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 5) SHEETS E-1 & M-1 BOTH SHOW A NEW ROOF TOP A/C |
| COMPRESSOR, SHEET M2 HAS CODE LANGUAGE FROM THE 2007 |
| FBC-B ABOUT ROOF MOUNTED A/C UNITS AND THE MINIMUM |
| HEIGHT OF THE STANDS LISTING TABLE 1509.7. PLEASE |
| UPDATE THE PLANS TO THE 2017 FBC-B TABLE 1510.10. IF |
| THE PIPE STAND DETAIL FOUND ON M2 IS TO BE USED THEN |
| PLEASE PROVIDE THE WELD INFORMATION MISSING FROM THE |
| PLANS AS WELL TO WHAT WIND SPEED DESIGN WAS USED FOR |
| THE ANCHORING OF THE ROOF TOP STAND TO THE ROOF FRAMING |
| MEMBERS AND THE ROOF TOP UNIT TO THE STAND. |
| 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| |
| WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| THE REFERENCED STANDARDS AT TIME OF INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2) QUALIFICATIONS OF WELDING PERSONAL |
| |
| 6) THE ARCHITECTURAL SHEETS DOES NOT SHOW A ROOF PLAN |
| BUT THE MECHANICAL SHEET M-1 DOES SHOW THE NEW ROOF TOP |
| COMPRESSOR. THE PLANS DO NOT INDICATE HOW YOU ARE TO |
| GAIN ACCESS ONTO THE ROOF. SHOW COMPLIANCE WITH: |
| 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS |
| OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR |
| THE ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO |
| CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO |
| ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR |
| EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS |
| SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER |
| THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS |
| HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 |
| UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL |
| NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS |
| INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL |
| BE MEASURED TO THE TOP OF THE PARAPET WALL. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |