Plan Review Notes For Permit 19020371 |
Permit Number |
19020371 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-02-25 13:50:01 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | ITEM #1 FROM THE LAST REVIEW IS STILL PENDING. THE | | OPTION FROM SECTION 5.6.4 OF THE PRODUCT APPROVAL # FL | | 1045-R10 HAS NOT BEEN SELECTED. PLEASE SEE NOTES BELOW | | FROM THE LAST REVIEW. | | | | 1 ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL | | FL10450 R10 SUBMITTED. CLEARLY SPECIFY IF THE | | UNDERLAYMENT IS GOING TO BE A DIRECT DECK UNDERLAYMENT | | OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING | | IS REQUIRED: | | A) FOR DIRECT BOND TO DECK SEE NOTE AT BOTTOM OF SEC. | | 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC. | | 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE | | WITH THE DESIGN PRESSURES OF SEC. R301.1 | | FBC RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T | | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT | | CAN NOT BE USED. | | B) FOR MECHANICALLY ATTACHED BASE SHEET SEE SECTION | | 5.6.2 AND PROVIDE MINIMUM FASTENING REQUIREMENTS FROM | | FRSA/TRI APRIL 2012 (04 12), APPENDIX A, TABLE 1. | | CLEARLY MARK TABLE 1 WITH PROPOSED FASTENING. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | |
|