2019-02-28 11:02:47 | MR. GOMEZ, |
| PLEASE SEE THE BELOW COMMENTS AND PLEASE LET ME KNOW IF |
| THEY WILL SUFFICE TO MOVE FORWARD WITH THIS PERMIT. |
| THANK YOU FOR YOUR ASSISTANCE. |
| KELLY |
| |
| GOOD AFTERNOON, |
| BELOW PLEASE FIND THE COMMENTS |
| |
| RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 1- ROOFING CONTRACTOR SUBMITTED FLORIDA PRODUCT |
| APPROVAL FOR SKYLIGHTS. SCOPE OF WORK IS NOT CLEAR. |
| ACCORDING TO CITY RECORDS, THIS HOUSE HAD NOT SKYLIGHTS |
| AT TIME OF CONSTRUCTION AND THERE ARE NOT RECORDS FOR |
| PERMIT APPLICATIONS FOR SKYLIGHT INSTALLATION. ALSO, |
| PAPA AERIAL VIEW DOESN'T SHOW SKYLIGHTS EITHER. FRAMING |
| AND INSTALLATION OF SKYLIGHTS CAN NOT BE DONE BY THE |
| ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSES A |
| LICENSE TO DO SO. SEE SEC. 489.113 F.S. NEED TO PROVIDE |
| COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE NEW |
| SKYLIGHT, INCLUDING LOCATION ON THE ROOF. AND, NEED |
| SEPARATE PERMIT OR SUB-PERMIT APPLICATION FOR THIS |
| ADDITIONAL SCOPE OF WORK. |
| |
| -WE WOULD LIKE TO WITHDRAWAL THE PRODUCT APPROVAL FOR |
| THE SKYLIGHTS PLEASE. WE WILL NOT BE COMPLETING ANY |
| SKYLIGHT WORK. *************** |
| |
| ORIGINAL COMMENT: |
| 2- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL |
| FL10450-R10 SUBMITTED. CLEARLY SPECIFY IF THE |
| UNDERLAYMENT IS GOING TO BE A DIRECT-DECK UNDERLAYMENT |
| OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING |
| IS REQUIRED: |
| A) FOR DIRECT-BOND TO DECK SEE NOTE AT BOTTOM OF SEC. |
| 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC. |
| 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE |
| WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T |
| MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT |
| CAN NOT BE USED. |
| |
| 5.6.1 UNDERLAYMENT IS GOING TO BE DIRECT-BOND TO DECK |
| 5.6.4 |
| #1 MAXIMUM DESIGN PRESSURE = -75.0 PSF: FIELD & |
| PERIMETER ************************* |
| #2 MAXIMUM DESIGN PRESSURE = -120.0 PSF: |
| CORNER************************************ |
| |
| ROOFPRO |
| 6555 GARDEN ROAD, SUITE 18 |
| RIVIERA BEACH, FL 33404 |
| 561-249-0247 |
| |
| WWW.ROOFPRO411.COM |
| |
| |
| |