2019-02-28 11:02:47MR. GOMEZ,
 PLEASE SEE THE BELOW COMMENTS AND PLEASE LET ME KNOW IF
 THEY WILL SUFFICE TO MOVE FORWARD WITH THIS PERMIT.
 THANK YOU FOR YOUR ASSISTANCE.
 KELLY
  
 GOOD AFTERNOON,
 BELOW PLEASE FIND THE COMMENTS
  
 RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ROOFING CONTRACTOR SUBMITTED FLORIDA PRODUCT
 APPROVAL FOR SKYLIGHTS. SCOPE OF WORK IS NOT CLEAR.
 ACCORDING TO CITY RECORDS, THIS HOUSE HAD NOT SKYLIGHTS
 AT TIME OF CONSTRUCTION AND THERE ARE NOT RECORDS FOR
 PERMIT APPLICATIONS FOR SKYLIGHT INSTALLATION. ALSO,
 PAPA AERIAL VIEW DOESN'T SHOW SKYLIGHTS EITHER. FRAMING
 AND INSTALLATION OF SKYLIGHTS CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSES A
 LICENSE TO DO SO. SEE SEC. 489.113 F.S. NEED TO PROVIDE
 COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE NEW
 SKYLIGHT, INCLUDING LOCATION ON THE ROOF. AND, NEED
 SEPARATE PERMIT OR SUB-PERMIT APPLICATION FOR THIS
 ADDITIONAL SCOPE OF WORK.
  
 -WE WOULD LIKE TO WITHDRAWAL THE PRODUCT APPROVAL FOR
 THE SKYLIGHTS PLEASE. WE WILL NOT BE COMPLETING ANY
 SKYLIGHT WORK. ***************
  
 ORIGINAL COMMENT:
 2- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL10450-R10 SUBMITTED. CLEARLY SPECIFY IF THE
 UNDERLAYMENT IS GOING TO BE A DIRECT-DECK UNDERLAYMENT
 OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING
 IS REQUIRED:
 A) FOR DIRECT-BOND TO DECK SEE NOTE AT BOTTOM OF SEC.
 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC.
 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT
 CAN NOT BE USED.
  
 5.6.1 UNDERLAYMENT IS GOING TO BE DIRECT-BOND TO DECK
 5.6.4
 #1 MAXIMUM DESIGN PRESSURE = -75.0 PSF: FIELD &
 PERIMETER *************************
 #2 MAXIMUM DESIGN PRESSURE = -120.0 PSF:
 CORNER************************************
  