2019-02-25 13:43:33 | ****CORRECTIONS**** |
| |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| ITEM # 1 FROM THE LAST REVIEW STILL HAS NOT BEEN |
| ADDRESSED. THE OPTION FROM SECTION 5.6.4 FROM THE |
| PRODUCT APPROVAL # FL 10450-R10 HAS NOT BEEN SELECTED. |
| PLEASE SEE COMMENT BELOW. |
| |
| ORIGINAL COMMENT: |
| 1? ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL |
| FL10450?R10 SUBMITTED. CLEARLY SPECIFY IF THE |
| UNDERLAYMENT IS GOING TO BE A DIRECT?DECK UNDERLAYMENT |
| OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING |
| IS REQUIRED: |
| A) FOR DIRECT?BOND TO DECK SEE NOTE AT BOTTOM OF SEC. |
| 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC. |
| 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE |
| WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| FBC?RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN?T |
| MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT |
| CAN NOT BE USED. |
| B) FOR MECHANICALLY ATTACHED BASE SHEET SEE SECTION |
| 5.6.2 AND PROVIDE MINIMUM FASTENING REQUIREMENTS FROM |
| FRSA/TRI APRIL 2012 (04?12), APPENDIX A, TABLE 1. |
| CLEARLY MARK TABLE 1 WITH PROPOSED FASTENING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |