Plan Review Notes
Plan Review Notes For Permit 19020368
Permit Number 19020368
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-21 11:36:08RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL10450-R10 SUBMITTED. CLEARLY SPECIFY IF THE
 UNDERLAYMENT IS GOING TO BE A DIRECT-DECK UNDERLAYMENT
 OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING
 IS REQUIRED:
  
 A) FOR DIRECT-BOND TO DECK SEE NOTE AT BOTTOM OF SEC.
 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC.
 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT
 CAN NOT BE USED.
  
 B) FOR MECHANICALLY ATTACHED BASE SHEET SEE SECTION
 5.6.2 AND PROVIDE MINIMUM FASTENING REQUIREMENTS FROM
 FRSA/TRI APRIL 2012 (04-12), APPENDIX A, TABLE 1.
 CLEARLY MARK TABLE 1 WITH PROPOSED FASTENING.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- OK.
  
 3- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  