Plan Review Notes
Plan Review Notes For Permit 19020335
Permit Number 19020335
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-11 10:52:01BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 THE FOLLOWING COMMENTS PERTAIN TO THE 50 X 115 TENT.
 SQUARE FOOTAGE - 5750. (THE BUILDING OFFICIAL HAS
 DETERMINED ANY TEMPORARY MEMBRANE STRUCTURE THAT HAS A
 SPAN OF 30 FEET IN ANY DIRECTION SHALL CONFORM THE THE
 FOLLOWING REQUIREMENTS)
 A. PROVIDE STRUCTURAL CONNECTION DETAILS SIGNED AND
 SEALED BY A DESIGN PROFESSIONAL. - NOT COMPLETE -
 INCLUDE FASTENER SCHEDULE FOR BASEPLATES. INCLUDE ALL
 TENTS ON SITE THAT HAVE A 30 FOOT SPAN OR GEATER. SIGN
 AND SEAL DOCUMENT. (PER B.O.)
 B. PROVIDE STRUCTURAL EVALUATIONS OF STRUCTURE SIGNED
 AND SEALED BY A DESIGN PROFESSIONAL. - NOT COMPLETE.
 CALCULATIONS TO COVER ALL TENTS ON SITE WITH SPANS OF
 30 FEET OR MORE. (PER B.O.)
  
 1. 3103.1 CONFORMANCE.
  
 1. PROVIDE STATEMENT FOR DATE OF ASSEMBLY AND DATE OF
 REMOVAL. - COMPLETE
 2. PROVIDE SITE PLAN. SHOW LOCATION OF PROPOSED
 STRUCTURE AND DISTANCE TO PROPERTY LINES AND OTHER
 STRUCTURES PER FBC CHPT. 6, SEC. 602. - COMPLETE
 3. CONFORMANCE REQUIREMENTS PER SEC. 3103.1.1
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? SUPPLIER TO
 PROVIDE CERTIFIED REPORT. - NOT COMPLETE - SEE ABOVE
 (B)
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701. - COMPLETE
 C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN
 REQUIRED. - NOT REQUIRED
  2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN - NOT
 APPLICABLE
  A) STATE OCCUPANT LOAD. - COMPLETE
  B) IDENTIFY MEANS OF EGRESS. NOT REQUIRED - OPEN
 TENT
  C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO
 EXIT. - NOT REQUIRED - OPEN TENT
 D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE
 PLAN - (SHOW ACCESSIBLE ROUTE TO ACCESSIBLE RESTROOMS
 (TEMPORARY OR PERMANENT)
 E. LIGHT 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
 - N/A
 F. VENTILATION 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1203 - N/A
 G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES
 ON SITE PLAN - COMPLETE
  2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.1 -
 COMPLETE
  
 ACCESSIBLE RESTROOMS SHALL BE PROVIDED WITHING 500 FEET
 OF TENT
  
 2. PROVIDE OCCUPANT LOAD. -COMPLETE
  
 3. STRUCTURE MAY QUALIFY AS A THREHOLD BUILDING PER
 F.S. 553.79 BASED ON SQUARE FOOTAGE AND OCCUPANT LOAD.
 THIS WILL BE DETERMINED UPON RECEIPT OF ADDITIONAL
 REQUIRED INFORMATION. - N/A
  
 4. PROVIDE STRUCTURAL DETAILS SIGNED AND SEALED BY A
 FLORIDA LICENSED PROFESSIONAL ENGINEER. - N/A
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved