2019-02-08 09:24:07 | PERMIT # 19020335 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| PASSED WITH COMMENTS: |
| |
| 1) A FIRE INSPECTION WILL BE CONDUCTED TO ENSURE |
| COMPLIANCE OF ALL APPLICABLE FIRE CODE REQUIREMENTS, |
| |
| 2) REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE THE |
| OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF |
| COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4). |
| |
| 3) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| |
| 4) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| BUILDING STRUCTURES. DRAWING PROVIDED IS NOT TO SCALE, |
| SO IT IS NOT POSSIBLE TO DETERMINE COMPLIANCE WITH THIS |
| REQUIREMENT. |
| |
| 5) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, |
| OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS |
| ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. |
| |
| 6) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| LOCATIONS. |
| |
| 7) GENERATORS AND OTHER INTERNAL COMBUSTION POWER |
| SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 |
| FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| ENCLOSURE. |
| |
| 8) THE OCCUPANT LOAD FOR THE 50' X 115' TENT SHALL |
| COMPLY WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER |
| NFPA 101: CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, |
| ASSEMBLY USE: LESS CONCENTRATED USE, WITHOUT FIXED |
| SEATING - 15 SQ FT/PERSON. |
| |
| |
| SUE ELLEN CALDERON |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| |