Plan Review Notes For Permit 19020308 |
Permit Number |
19020308 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-02-08 10:17:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS A FIRE ALARM PLAN SUBMITTED WITH THIS | | PACKET THAT IS UNREADALBE. | | | | PLEASE CLARIFY IF THIS IS FOR FIRE ALARM OR DOOR | | REPLACEMENT. IF THIS IS NOT A FIRE ALARM MODIFICATION, | | DO NOT USE FIRE ALARM PLANS. | | | | | | | | 2) THERE IS NO DOOR SCHEDULE THAT CLEARLY INDICATES | | DOOR SIZE, HARDWARE, TYPE, SWING, ETC. | | | | | | | | 3) PLEASE ENLARGE THE DOOR AREA DRAWING TO CLEARLY | | DEFINE SWING AND PATH OF TRAVEL. | | | | | | | | 4) CARD READER ACCESS IS INDICATED, PLEASE CLARIFY AT | | WHICH DOORS. | | | | LOW VOLTAGE FOR CARD READER SHALL BE UNDER SEPARATE | | SHOP DRAWINGS AND PERMIT. | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|