Plan Review Notes For Permit 19020260 |
Permit Number |
19020260 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-02-08 15:25:39 | NFPA 72-10.18.2.4, 2010 VERIFICATION OF COMPLIANT | | INSTALLATION. WHERE REQUIRED, COMPLIANCE OF THE | | COMPLETED INSTALLATION WITH THE REQUIREMENTS OF THIS | | CODE, AS IMPLEMENTED VIA THE REFERRING CODE(S), | | SPECIFICATIONS, AND/OR OTHER CRITERIA APPLICABLE TO THE | | SPECIFIC INSTALLATION, SHALL BE CERTIFIED BY A | | QUALIFIED AND IMPARTIAL THIRD-PARTY ORGANIZATION | | ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. | | | | 10.18.2.4.1 VERIFICATION SHALL ENSURE THAT THE | | INSTALLED SYSTEM INCLUDES ALL COMPONENTS AND FUNCTIONS, | | THAT THOSE COMPONENTS AND FUNCTIONS ARE INSTALLED AND | | OPERATE AS REQUIRED, THAT THE SYSTEM HAS BEEN 100 | | PERCENT ACCEPTANCE TESTED IN ACCORDANCE WITH CHAPTER | | 14, AND THAT ALL REQUIRED DOCUMENTATION HAS BEEN | | PROVIDED TO THE SYSTEM OWNER. | | EXCEPTION: WHERE THE INSTALLATION IS AN EXTENSION, | | MODIFICATION, OR RECONFIGURATION OF AN EXISTING SYSTEM, | | THE VERIFICATION SHALL BE REQUIRED FOR THE NEW WORK | | ONLY, AND RE-ACCEPTANCE TESTING IN ACCORDANCE WITH | | CHAPTER 14 SHALL BE ACCEPTABLE. | | | | INSTALLATION SHALL COME INTO COMPLIANCE WITH NFPA 70, | | 72. |
|