2019-03-04 16:14:02 | 1ST REVIEW: FBC 2017 6TH EDITION |
| 1ST REVIEW FBC 2017 EXISTING BUILDING |
| |
| THE PERMIT APPLICATION APPEARS TO BE TO ALTER THE USE |
| OF SPACE THAT MAY NEVER HAVE PREVIOUSLY RECEIVED A |
| CERTIFICATE OF OCCUPANCY. PLEASE CHECK WITH CDS |
| CUSTOMER SERVICE SPECIALIST CRAIG MCPHERSON AT 561 |
| 805-6684 FOR A CERTIFICATE OF OCCUPANY FOR THIS SPACE |
| IDENTIFIED AS THE 7TH FLOOR. THE PLANS ARE DEFICIENT AS |
| THEY DO CONTAIN ADEQUATE INFORMATION TO DETERMINE THE |
| INTENDED USE OF THE SPACE OR THE PREVIOUSLY APPROVED |
| USE. PLEASE PROVIDE DRAWINGS OF ARCHITECTURAL QUAITY |
| (NOT NECESSARILY SIGNED & SEAL BY AN ARCHITECT) TO |
| DETERMINE THE INTENDED USE AND PROVIDE MINIMUM CODE |
| DATE RELATIVE TO THE BUILDING SUCH AS TYPE OF |
| CONSTRUCTION AND A LIFE SAFETY PLAN SHOWING EXITING |
| STRATEGY AND THE EXISTENCE OF EXITING AND FIRE |
| SUPPRESSION SYSYTEMS. PROVIDE AT A MINIMUM PROVIDE THE |
| APPLICABLE CODE IN EFFECT AND LEVEL OF ALTERATION, |
| OCCUPANCY CLASSIFICATION, OCCUPANT LOAD. PRESUMABLE THE |
| SPACE MAY HAVE BEE APPROVED FOR A STORAGE USE. THIS |
| WOULD RESULT IN A LOW OCCUPANT LOAD. EXISTING EXITS AND |
| BATHROOM FACILITIES MAY BE SUFFICIENT, BUT THE PLAN |
| DOES NOT ADDRESS EITHER MATTER. PLEASE PROVIDE RELATIVE |
| INFORMATION. |
| |
| FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| IT IS NOTED THAT THIS APPLICATION IS APPLIED FOR BY A |
| FENCE CONTRACTOR. APPLICATIONS OF THIS NATURE IS |
| REQUIRED TO BE MADE BY A BUILDING OR GENERAL |
| CONTRACTOR. |
| |