2019-03-06 10:41:44 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. 1106 FBC-EXISTING BUILDING. AND SEC. R101.4.2 |
| AND R101.5 FBC-ENERGY CONSERVATION. NOTE: COORDINATE |
| WITH PLANS AND PRODUCT APPROVALS SUBMITTED TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 2- PLANS NEED TO PROVIDE COMPLIANCE WITH THE HEATING |
| REQUIREMENTS FOR NEW ROOM AS REQUIRED BY SEC. R303.10 |
| FBC-RESIDENTIAL. (NOTE: MECHANICAL PERMIT MAY BE |
| REQUIRED). |
| |
| 3- WALL SECTION 1/7 ON SHEET 7 OF 8: |
| A) R-30 BATT INSULATION DOESN'T FIT ON A 2" X 8" ROOF |
| RAFTERS. THE THICKNESS OF R-30 BATT INSULATION IS MORE |
| OR LESS 9-1/2" THICK. REVISE AS REQUIRED. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| B) SHOW COMPLIANCE WITH NEW ROOF CROSS VENTILATION AS |
| REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. NOTE: |
| INSULATION CAN NOT BLOCK THE CROSS VENTILATION. SEE |
| SEC. R8016.3 FBC-RESIDENTIAL. COORDINATE WITH ITEM |
| #3(A) ABOVE. |
| |
| C) CLARIFY IF THE NEW ROOM IS GOING TO BE AIR |
| CONDITIONED. IF SO, THEN PROVIDE DETAILS AND |
| SPECIFICATIONS FOR THE INSULATION BETWEEN THE EXISTING |
| NON-A/C STORAGE ROOM AND THE NEW ROOM AS REQUIRED BY |
| SEC. R103.2 FBC-RESIDENTIAL. ALSO, PROVIDE |
| SPECIFICATIONS FOR INSULATION ON NEW EXTERIOR WOOD |
| FRAMED WALL. |
| |
| D) SPECIFY RING SHANK NAILS FOR ROOF SHEATHING AS |
| REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL. |
| |
| 4- SHEET 6 OF 8 IS MISSING THE ENGINEER' SEAL AS |
| REQUIRED BY CHAPTER 471 F.S. |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| B)FRENCH DOORS. PROVIDE FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND PROVIDE 2 COPIES OF COMPLETE PRODUCT APPROVAL. |
| ONLY ONE COPY WAS SUBMITTED. SEC. 107.1 CITY |
| AMENDMENTS. |
| |
| C)SINGLE HUNG WINDOWS. PROVIDE 2 COPIES. ONLY ONE COPY |
| WAS SUBMITTED. SEC. 107.1 CITY AMENDMENTS. |
| |
| 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 7- PROVIDE COMPLETE WALL SECTION FOR NEW EXTERIOR WOOD |
| FRAME WALL : SPECIFY ALL INTERIOR AND EXTERIOR FINISH |
| MATERIALS. SPECIFY WALL SHEATHING TYPE AND FASTENERS. |
| SPECIFY THE 2 REQUIRED WATER-RESISTIVE BARRIERS AS |
| REQUIRED BY SE. R703.7.3 FBC-RESIDENTIAL. IF STUCCO |
| FINISH, THEN SPECIFY STUCCO THICKNESS AS REQUIRED BY |
| TABLE R702.1(1) FBC-RESIDENTIAL. |
| |
| 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH THE WIND |
| RESISTANCE AS REQUIRED BY SEC. R703.1.2.1 |
| FBC-RESIDENTIAL. |
| |
| 9-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WAS UPDATED TO $32,964. THE |
| PERMIT FEE BALANCE IS $722.20. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |