Date Text
2019-04-18 11:19:08APPROVED
 PROVISO
  
 1. VENT FOR WATER CLOSET AND TUB/SHOWER IN SECOND BATH
 SHALL RISE VERTICALLY FROM THE FIXTURE DRAIN TO WHICH
 IT IS CONNECTED TO A POINT 6" ABOVE THE FLOOD LEVEL RIM
 OF THE FIXTURES BEING VENTED PER FBC RES P3104.3. SEE
 RED LINED COMMENT AND CORRECTED SECTION ON P-1 SANITARY
 RISER DIAGRAM
  
 NOTE: A SEPARATE APPLICATION FOR GAS PERMIT IS REQUIRED
 PER WPB FBC 105.1.PROVIDE WITH SEPARATE GAS PERMIT
 APPLICATION THE FOLLOWING PER WPB FBC 107.2.1
 A. SUBMIT GAS RISER DIAGRAM THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES
 G2413.4.1 AND G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF ANY
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE.
 3. TYPE OF GAS (LP OR NATURAL).
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO FBC FG SECS. 401.8,
 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR FBC RES
 SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH
 G2413.4 (21). PROVIDE ON THE PLANS THE TABLES USED FOR
 CALCULATIONS AND/OR TWO COPIES OF SAID TABLES..
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER FBC FG
 SEC.402.4.1, 402.4.2, FBC RES. SEC. G 2413.4.1 AND
 G2413.4.2.
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR IF APPLICABLE
 (IE. A RANGE OR CLOTHES DRYER) PER FBC FG SEC.304.1 AND
 614.6 (CLOTHES DRYERS) OR FBC RES. SEC. G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 8. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS AND
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 SEC. 402.2, AND 301.3 OR FBC RES SEC. G2404.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 9. SHOW THE LOCATIONS OF THE GAS METER AND THE WATER
 HEATER ON PLAN SHEET A-1.
  
  