Date |
Text |
2019-04-18 11:19:08 | APPROVED |
| PROVISO |
| |
| 1. VENT FOR WATER CLOSET AND TUB/SHOWER IN SECOND BATH |
| SHALL RISE VERTICALLY FROM THE FIXTURE DRAIN TO WHICH |
| IT IS CONNECTED TO A POINT 6" ABOVE THE FLOOD LEVEL RIM |
| OF THE FIXTURES BEING VENTED PER FBC RES P3104.3. SEE |
| RED LINED COMMENT AND CORRECTED SECTION ON P-1 SANITARY |
| RISER DIAGRAM |
| |
| NOTE: A SEPARATE APPLICATION FOR GAS PERMIT IS REQUIRED |
| PER WPB FBC 105.1.PROVIDE WITH SEPARATE GAS PERMIT |
| APPLICATION THE FOLLOWING PER WPB FBC 107.2.1 |
| A. SUBMIT GAS RISER DIAGRAM THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES |
| G2413.4.1 AND G2413.4.2. |
| 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF ANY |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. |
| 3. TYPE OF GAS (LP OR NATURAL). |
| 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO FBC FG SECS. 401.8, |
| 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR FBC RES |
| SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH |
| G2413.4 (21). PROVIDE ON THE PLANS THE TABLES USED FOR |
| CALCULATIONS AND/OR TWO COPIES OF SAID TABLES.. |
| 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER FBC FG |
| SEC.402.4.1, 402.4.2, FBC RES. SEC. G 2413.4.1 AND |
| G2413.4.2. |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR IF APPLICABLE |
| (IE. A RANGE OR CLOTHES DRYER) PER FBC FG SEC.304.1 AND |
| 614.6 (CLOTHES DRYERS) OR FBC RES. SEC. G 2407.1 AND |
| G2439.4 (CLOTHES DRYERS). |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| 8. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS AND |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG |
| SEC. 402.2, AND 301.3 OR FBC RES SEC. G2404.3. GAS |
| APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| SEC.305.1, FBC-RES. SEC.G2408.1. |
| 9. SHOW THE LOCATIONS OF THE GAS METER AND THE WATER |
| HEATER ON PLAN SHEET A-1. |
| |
| |