Plan Review Notes
Plan Review Notes For Permit 19020201
Permit Number 19020201
Review Stop B
Sequence Number 2
Notes
Date Text
2019-05-13 14:45:56NEW SINGLE FAMILY RESIDENCE (R3), SECOND REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 RESPONSE:
 BASED ON DRAWINGS SUBMITTED WITH THE PROPOSED POOL AND
 BRICK PATIO, THE REAR PROPERTY REQUIRES MORE ATTENTION.
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN FOR
 ENTIRE LOT AS REQUIRED BY SEC. 110.9 CITY AMENDMENTS.
  
 2- OK.
  
 3- A) OK.
  
 B) THE TREAD DEPTH SHALL BE MEASURED HORIZONTALLY
 BETWEEN THE VERTICAL PLANES OF THE FOREMOST PROJECTION
 OF ADJACENT TREADS. REVISE DIMENSIONS SHOWN ON STAIR
 SECTION 'A' ON SHEET A-2. THEY ARE MEASURED FROM THE
 VERTICAL PLAN OF THE RISER TO THE END OF THE NOSING.
  
 RESPONSE:
 TREAD DIMENSION IS NOT MEASURED PROPERLY. NEED TO
 MEASURE FROM THE VERTICAL PLANES (RISER TO RISER). THE
 NOSING DIMENSION AND TREAD DIMENSION SHOWN ON BOTH
 STAIRS DETAILS DETAILS DON'T MATCH. REVISE AS REQUIRED
 TO MATCH.
  
 4- SHEET A-2:
 A) OK.
  
 B)OK.
  
 C)OK.
  
 D) OK.
  
 5- A)ACCORDING TO FIGURE R301.2(7) OF FBC-RESIDENTIAL
 THE MINIMUM DIMENSION "A" FOR WALL AND ROOF END ZONE IS
 4 FT NOT 3.5 FT. REVISE THIS DIMENSION ON SHEET A-3 AND
 S-3.
 NOTE: WALL ELEVATION ON SHEET A-3 SPECIFIES A=3'-6".
 REVISE AS REQUIRED.
  
 RESPONSE:
 NOT ADDRESSED.
  
 B) OK.
  
 C) OK.
  
 6- OK.
  
 7- A) PROVIDE SPECIFICATIONS FOR THE INSULATION BETWEEN
 THE GARAGE AND THE A/C AREA OF THE MAIN HOUSE. SEC.
 R103.2 FBC-ENERGY CONSERVATION. COORDINATE WITH ENERGY
 CALCULATIONS.
  
 RESPONSE:
 PLANS DON'T SHOW ANY INSULATION BETWEEN THE GARAGE AND
 A/C AREA.
  
 B) PROVIDE THE MANUFACTURER'S SPECIFICATION S FOR
 WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON
 ITEM #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 INFORMATION SUBMITTED DOESN'T MATCH PRODUCT APPROVALS
 SUBMITTED. THE INFORMATION SUBMITTED IS FOR ANOTHER
 WINDOW MODEL. IT DOESN'T MATCH THE MODEL SHOWN ON THE
 PRODUCT APPROVAL SUBMITTED.
  
 8- PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE CEILING AT THE PATIO AREA. SEC.
 R703.1.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 PLANS DON'T SHOW ANY DETAILS.
  
 9- OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13-
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) INSWING ENTRY DOOR AS SHOWN ON PLANS. FLORIDA
 PRODUCT APPROVAL FL22383-R1 SUBMITTED WAS DENIED. NEED
 TO PROVIDE CURRENT PRODUCT APPROVAL AND ALSO PROVIDE
 THE INSTALLATION DRAWINGS THAT CORRESPOND TO THIS
 PRODUCT APPROVAL.
  
 RESPONSE:
 INFORMATION FROM TWO DIFFERENT MANUFACTURER'S WAS
 SUBMITTED. CLEARLY MARK THE ENTRY DOOR AND THE GARAGE
 SIDE DOOR AND PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE AND
 CORRESPONDING DRAWINGS.
  
 B) GARAGE OUTSIDE SWING DOOR. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE (TWO COPIES) THAT CORRESPONDS TO
 DRAWINGS SUBMITTED.
  
 RESPONSE:
 INFORMATION FROM TWO DIFFERENT MANUFACTURER'S WAS
 SUBMITTED. CLEARLY MARK THE ENTRY ODOR AND THE GARAGE
 SIDE DOOR AND PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE AND
 CORRESPONDING DRAWINGS.
  
 C)OK.
  
 D)OK.
  
 E) OK.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 (A)ENGINEER'S LETTER LISTING ALL THE PRODUCT APPROVALS
 IS MISSING THE ENGINEER'S TITLE BLOCK WITH ALL HIS
 INFORMATION. CHAPTER 471 F.S.
  
 (B)PRODUCT APPROVALS LISTED DON'T MATCH PRODUCT
 APPROVALS SUBMITTED. REVISE AS REQUIRED TO MATCH.
  
 16- OK.
  
 17 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  