Plan Review Notes
Plan Review Notes For Permit 19020201
Permit Number 19020201
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-07 10:01:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 A SEPARATE GAS PERMIT IS REQUIRED PER WPB FBC 105.1.
 PEASE SEE NOTES LISTED AFTER PLUMBING COMMENTS.
  
 1ST REVIEW
 PLUMBING COMMENTS:
 DENIED
 PLAN SHEET P-1
 1. PLAN SHALL INCLUDE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN PER WPB FBC 107.2.1
 2. SANITARY RISER DIAGRAM
 A. POWDER ROOM WATER CLOSET FIXTURE DRAIN SHALL BE
 VENTED PER FBC RES P3102.2.1.
 B. VENT FOR WATER CLOSET AND TUB/SHOWER IN SECOND BATH
 SHALL RISE VERTICALLY FROM THE FIXTURE DRAIN TO WHICH
 IT IS CONNECTED TO A POINT 6" ABOVE THE FLOOD LEVEL RIM
 OF THE FIXTURES BEING VENTED PER FBC RES P3104.3.
 C. SANITARY RISER CALLS OUT A SHOWER IN THE SECOND
 BATH. PLAN SHEET A-2 SHOWS A BATHTUB. PIEASE CLARIFY
 PER WPB FBC 107.2.1.
 D. PROVIDE AN INDIVIDUAL VENT FOR THE WASHER PER FBC
 RES P3102.2.1 AND P3107.1 WHICH LIMITS COMMON VENTING
 TO TWO (2) TRAPS OR TRAPPED FIXTURES.
 E. EACH OF THE TWO (2) LAVATORIES IN THE MASTER BATHIS
 S-TRAPPED WHICH IS PROHIBITED PER FBC RES P3105.1 AND
 P3201.5. PROVIDE INDIVIDUAL VENTS FOR P3101.2.1,
 P3104.1 AND P3114.
 F. PROVIDE DRAIN AND VENT FOR THE KITCHEN SINK SHOWN ON
 A-1.
 3. PROVIDE WITH THE APPLICATION FOR A GAS PERMIT THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL
 FOR THE GAS WATER HEATER SHOWN ON PLAN SHEET A/C-1 PER
 WPB FBC 107.2.1.
  
 END OF PLUMBING COMMENTS
  
 RE: GAS PERMIT APPLICATION.
 PROVIDE WITH SEPARATE GAS PERMIT APPLICATION THE
 FOLLOWING PER WPB FBC 107.2.1
 1. SUBMIT GAS RISER DIAGRAM THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES
 G2413.4.1 AND G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF ANY
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE.
 3. TYPE OF GAS (LP OR NATURAL).
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO FBC FG SECS. 401.8,
 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR FBC RES
 SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH
 G2413.4 (21). PROVIDE ON THE PLANS THE TABLES USED FOR
 CALCULATIONS AND/OR TWO COPIES OF SAID TABLES..
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER FBC FG
 SEC.402.4.1, 402.4.2, FBC RES. SEC. G 2413.4.1 AND
 G2413.4.2.
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR IF APPLICABLE
 (IE. A RANGE OR CLOTHES DRYER) PER FBC FG SEC.304.1 AND
 614.6 (CLOTHES DRYERS) OR FBC RES. SEC. G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 SEC. 402.2, AND 301.3 OR FBC RES SEC. G2404.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 9. SHOW THE LOCATIONS OF THE GAS METER AND THE WATER
 HEATER ON PLAN SHEET A-1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  