Plan Review Notes For Permit 19020201 |
Permit Number |
19020201 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-11 13:53:01 | MECHANICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. CONTRACTOR SHALL SIGN PLAN. | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | SECTION 107.3.5) AND F.S. 481.229. | | | | 2. IDENTIFY LOCATION OF CONDENSATE LINE PER FBC | | M1411.3. | | | | 3. LOCKING ACCESS PORT CAPS REQUIRED PER FBC M1411.8. | | | | 4. PROVIDE DETAIL FOR EXTERIOR INSTALLATION OF | | CONDENSING UNIT PER FBC M1401.4. | | | | | | | | |
|