Date |
Text |
2019-02-27 12:45:39 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| RE E3606.3 |
| 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS, BASED ON FORMULA PROVIDED IN FBC RESIDENTIAL. |
| NEC 220; FBC RE E3602.2 |
| 3. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN |
| EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE |
| CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| 4. EXTERIOR RECEPTACLE ON PATIO IS REQUIRED TO BE GFCI |
| PROTECTED. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| E3902.3 |
| 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1 |
| 7. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| 8. NO PARTS OF CORD-CONNECTED LUMINAIRES, CHAIN-, |
| CABLE-, OR CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, |
| PENDANTS, OR CEILING-SUSPENDED (PADDLE) FANS SHALL BE |
| LOCATED WITHIN A ZONE MEASURED 3 FEET HORIZONTALLY AND |
| 8 FEET VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR |
| SHOWER STALL THRESHOLD. PROVIDE CORRECTION FOR MASTER |
| BATH. NEC 410.10(D); FBC RE E4003.11 |
| 9. PLEASE PROVIDE ORIGINAL SIGNATURE ON PLAN OF PERSON |
| RESPONSIBLE FOR DESIGN, A PHOTOCOPY OF SIGNATURE IS NOT |
| ACCEPTABLE. WPB FBC 107.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |
| |