2020-08-19 11:43:44 | INCOMPLETE APPLICATION |
| |
| PERMIT 19020197 - UNDERGROUND FIBER MCIMETRO PROJECT |
| #1801CVFF.244 CLEMATIS TO OKEECHOBEE 3RD SUBMITTAL |
| |
| PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE |
| DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401 |
| OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE |
| COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION. |
| THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO |
| REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF |
| HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS, |
| THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION, |
| NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE |
| APPROVED. |
| |
| 1) ENGINEERING PLANS - |
| |
| A. THE ENGINEERING PLANS MUST SHOW THE COMPLETED AND |
| PROPOSED RIGHT-OF-WAY IMPROVEMENTS FOR THE CLEMATIS |
| STREET RECONSTRUCTION PROJECTS AND THE PROPOSED |
| RECONSTRUCTION OF THE ALLEY SOUTH OF CLEMATIS STREET. |
| STAFF NEEDS TO VERIFY THAT THE PROPOSED FIBER CONDUIT, |
| HANDHOLDS AND FUTURE COMMUNICATION POLES DO NOT |
| INTERFERE WITH THESE APPROVED, PROPOSED AND CONSTRUCTED |
| RIGHT-OF-WAY PROJECTS. |
| |
| B. THE LOCATIONS OF THE TREES WITHIN THE DATURA ST. |
| RIGHT-OF-WAY AND THEIR ROOT ZONES NEED TO BE SHOWN. THE |
| FIBER BORE NEEDS TO BE CLEARLY SHOWN AVOIDING DAMAGE TO |
| THE ROOT ZONES (THIS MAY OCCUR ON THE ENGINEERING |
| PLAN). THE ENGINEERING PLAN NEEDS TO SHOW THE TREES AND |
| A TEN (10) FOOT SETBACK FROM THE TREES TO THE HANDHOLES |
| IN ORDER TO PREVENT DAMAGE TO THE TREES OR THEIR ROOT |
| ZONES FROM BOTH THE BORE AND THE HANDHOLE INSTALLATION. |
| THE BORE DEPTH SHOWN AT FIVE (5) FEET BELOW GRADE IS AT |
| A SUFFICIENT DEPTH TO GO UNDER THE TREE ROOTS; HOWEVER, |
| WHERE THE BORE SLOPES UP TO THE HANDHOLE IT MAY NOT |
| DAMAGE THE ROOT ZONE. |
| |
| 2) SURVEY OF UNDERGROUND FACILITIES |
| |
| A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON THE |
| SURVEY. SINCE THIS WAS JUST RECENTLY REDONE THE |
| AS-BUILTS SHOULD BE AVAILABLE FROM THE CITY'S |
| ENGINEERING DEPARTMENT. |
| |
| PLEASE NOTE: |
| |
| THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811 |
| TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL |
| DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES MUST |
| BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE |
| WORK. |
| |
| THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A |
| CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE |
| WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES |
| THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS, |
| OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |