2019-03-29 09:37:40 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| JOSEAN A. DUPREY E.I., BN, PX |
| BUILDING PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6716 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 2ND REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. CORRECTED |
| |
| PREVIOUS COMMENTS: |
| |
| 1A. THE REPAIR DETAILS MUST BE SIGNED BY THE ENGINEER. |
| FBC 107 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER |
| AND SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL |
| SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN. |
| CODE RULE 61G15-23.001 |
| WHEN AN ENGINEER MUST SEAL, SIGN AND DATE ENGINEERING |
| SPECIFICATIONS OR CALCULATIONS UNDER THE PROVISIONS OF |
| SECTION 471.025, F.S., AND SUBSECTION (1) OF THIS RULE, |
| AN INDEX SHEET FOR ENGINEERING SPECIFICATIONS AND |
| CALCULATIONS MAY BE USED. THE INDEX SHEET MUST BE |
| SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL |
| ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND |
| PREPARATION OF EACH SECTION OF THE ENGINEERING |
| SPECIFICATIONS OR CALCULATIONS, WITH SUFFICIENT |
| INFORMATION ON INDEX SHEET SO THAT THE USER WILL BE |
| AWARE OF EACH PORTION OF THE SPECIFICATIONS OR |
| CALCULATIONS FOR WHICH EACH PROFESSIONAL ENGINEER IS |
| RESPONSIBLE. |
| |
| 2. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND |
| SUBMITTED IN TRIPLICATE. ONLY TWO COPIES WERE PROVIDED |
| AND ONLY ONE COPY HAVE THE CONTRACTOR INFORMATION AND |
| SIGNATURE. |
| CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM |
| BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER |
| 468, PART XII |
| |
| 3. CORRECTED |
| |
| 4. CORRECTED |
| |