2019-02-11 13:29:56 | 1) SUBMIT TWO COPIES OF A LEGIBLE GAS PLAN. THE |
| SUBMITTED DRAWINGS ARE REDUCED SO MUCH THAT THEY ARE |
| ILLEGIBLE.WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 2). SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 |
| FBC-R SEC. G2413.4.1, G2413.4.2. |
| |
| 3). SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING |
| |
| (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| FBC SEC.107.2.1. |
| |
| 4). SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. |
| |
| 5). LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| G2413.4 (1 ) THROUGH G2413.4 (21). |
| |
| 6). SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| SEC. G 2413.4.1, G2413.4.2. |
| |
| 7). SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| |
| 8). INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| |
| 9.) SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| |
| 10) SUBMIT TWO COPIES OF A LEGIBLE HOUSE PLAN SHOWING |
| THE LOCATION OF THE TANKLESS WATER HEATER AND THE |
| LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS |
| IN RELATION TO THE WATER HEATER. THE LOCATION OF THE |
| WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. |
| |
| 11) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS |
| ( IF APPLICABLE). A LISTED SHUTOFF VALVE SHALL BE |
| INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 |
| FBC-FUEL GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| |
| 12) ) SUBMIT MANUFACTURER?S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS ( |
| IF APPLICABLE) . REGULATORS INSTALLED ON THE EXTERIOR |
| OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. IDENTIFY ON THE SPECIFICATION SHEETS |
| WHICH MODEL REGULATOR IS BEING INSTALLED AND THE |
| ORIFICE SIZE TO ENSURE THE REGULATOR CAN ACCOMMODATE |
| THE BTU LOAD THROUGH THE REGULATOR.2017 FGC SEC.410.1, |
| 2017 FBC-RES. SEC. G2421.1. |
| |