Plan Review Notes
Plan Review Notes For Permit 19020044
Permit Number 19020044
Review Stop Z
Sequence Number 2
Notes
Date Text
2019-06-19 13:47:11FAILED
  
 1) THANK YOU FOR PROVIDING THE SURVEY. THE SITE PLAN -
 ELECTRICAL DOES NOT MATCH THE SITE LAYOUT SHOWN ON THE
 SURVEY. THE SITE PLAN BASE MUST MATCH THE SURVEY AND
 THEN THE LIGHTS NEED TO BE PLACED TO AVOID THE TREES.
  
 2) REPEAT COMMENT: THE PLANS STATE THAT THE POLES WILL
 BE REMOVED AND REPLACED. ALL NEW POLES ARE REQUIRED TO
 MEET THE FIVE (5) FOOT SETBACK REQUIRED IN THE GENERAL
 COMMERCIAL ZONING DISTRICT. PROVIDE THE SETBACK
 DIMENSIONS FOR ALL THE PERIMETER POLES ON THE SITE PLAN
 SHOWING COMPLIANCE WITH THE FIVE (5) FOOT SETBACK
 REQUIREMENT.
  
 3) THE SITE PLAN SHOWS THE NORTHERNMOST POLE TYPE E
 ALONG CONGRESS AVENUE IN CONFLICT WITH AN EXISTING
 TREE, WHEN COMPARED TO THE SURVEY.
  
 4) THE SITE PLAN SHOWS ALL OF THE POLES ALONG THE
 NORTHERN PROPERTY LINE IN THE ALLEY, WHEN COMPARED TO
 THE SURVEY.
  