Plan Review Notes For Permit 19020044 |
Permit Number |
19020044 |
|
Review Stop |
Z |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-06-19 13:47:11 | FAILED | | | | 1) THANK YOU FOR PROVIDING THE SURVEY. THE SITE PLAN - | | ELECTRICAL DOES NOT MATCH THE SITE LAYOUT SHOWN ON THE | | SURVEY. THE SITE PLAN BASE MUST MATCH THE SURVEY AND | | THEN THE LIGHTS NEED TO BE PLACED TO AVOID THE TREES. | | | | 2) REPEAT COMMENT: THE PLANS STATE THAT THE POLES WILL | | BE REMOVED AND REPLACED. ALL NEW POLES ARE REQUIRED TO | | MEET THE FIVE (5) FOOT SETBACK REQUIRED IN THE GENERAL | | COMMERCIAL ZONING DISTRICT. PROVIDE THE SETBACK | | DIMENSIONS FOR ALL THE PERIMETER POLES ON THE SITE PLAN | | SHOWING COMPLIANCE WITH THE FIVE (5) FOOT SETBACK | | REQUIREMENT. | | | | 3) THE SITE PLAN SHOWS THE NORTHERNMOST POLE TYPE E | | ALONG CONGRESS AVENUE IN CONFLICT WITH AN EXISTING | | TREE, WHEN COMPARED TO THE SURVEY. | | | | 4) THE SITE PLAN SHOWS ALL OF THE POLES ALONG THE | | NORTHERN PROPERTY LINE IN THE ALLEY, WHEN COMPARED TO | | THE SURVEY. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | [email protected] |
|