2019-04-11 15:00:42 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #19020031 |
| 4/11/19 |
| |
| COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT |
| ADDRESSED- NO CORRECTIONS WERE MADE TO THE PLANS AND NO |
| RESPONSE NARRATIVE ADDRESSING THE COMMENTS WAS |
| SUBMITTED. |
| |
| PLEASE REVIEW THE COMMENTS LISTED BELOW AND COMPLY. |
| |
| |
| 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19020031 |
| 3/1/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M100: PLEASE PROVIDE A SCOPE OF WORK OUTLINE |
| ON THE PLAN- SECTION 107.2.1 WPB. |
| |
| 2) M100: BASED ON THE ARCHITECTURAL PLANS, THE PROPOSED |
| PROJECT APPEARS TO BE A CHANGE OF OCCUPANCY, OR A LEVEL |
| III ALTERATION AS INDICATED ON LS100. REFER TO SECTION |
| 809.2 FBC-17 EXISTING BUILDING CODE AND PROVIDE MINIMUM |
| VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER |
| TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE |
| THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF |
| OUTDOOR AIR. |
| |
| 3) M100: THE PLAN APPEARS TO SHOW A NEW 5-TON AC SYSTEM |
| WITH THE AIR HANDLER BEING INSTALLED IN THE ATTIC. |
| PLEASE SEE SECTION C403.2.9.6 FBC EC WHICH PROHIBITS |
| INSTALLATION OF AIR HANDLERS IN ATTICS. |
| |
| 3) M100: A DUCT SMOKE DETECTORS IS REQUIRED IN THE |
| SUPPLY AIR SYSTEMS OF THE NEW 5-TON AC SYSTEM PER |
| SECTION 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE |
| APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE |
| THE SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS |
| OF SUPPLY AIR. |
| |
| 4) M100: PROVIDE THE DIMENSIONS OF THE RETURN GRILLS IN |
| THE OFFICES- SECTION 603 FBC M. |
| |
| 5) M100: PROVIDE AIR DEVICE AND AIR DISTRIBUTION |
| SCHEDULES THAT INDICATE THE MAKES AND MODELS OF THE |
| DIFFUSERS AND GRILLS, AND TYPE OF DUCTWORK TO BE |
| INSTALLED- SECTION 603. |
| |
| 6) M100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| FLOOR GRILLS IN COMPLIANCE WITH SECTION 603.18.1 FBC M. |
| THE SPECS MUST INDICATE THE GRILLS SHALL RESIST |
| STRUCTURAL FAILURE AS OUTLINED IN THE SECTION. |
| |
| 7) M100: PROVIDE A BATH AND TOILET ROOM EXHAUST FAN |
| SCHEDULE, AND SHOW THE EXHAUST DUCT RUNS AND |
| TERMINATION LOCATIONS- TABLE 403.3.1.1 FBC M. |
| |
| 8) M100: PROVIDE EQUIPMENT SCHEDULES AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS FOR ANY COOKING |
| APPLIANCES TO BE INSTALLED IN THE KITCHEN AND BAR- |
| SECTION 917 FBC M. PLEASE IDENTIFY THE LOCATIONS OF THE |
| APPLIANCES ON THE PLAN AND PRPOVIDE LOCAL EXHAUST |
| SYSTEMS (HOODS) WHERE REQUIRED. PLEASE NOTE THAT |
| SEPARATE PERMITS ARE REUIRED FOR GREASE EXHAUST |
| SYSTEMS- SECTION 107.2.1 WPB. |
| |
| 9) M100: EXHAUST VENTILATION IS REQUIRED FOR THE |
| KITCHEN AT A RATE OF 25 CFMS CONTINUOUSLY OR 100 CFMS |
| INTERMITTENTLY IN ACCORDANCE WITH TABLE 403.3.1.1 FBC |
| M. PLEASE NOTE FOOTNOTE B PROHIBITS RECIRCULATION OF |
| AIR FROM THE KITCHEN TO OTHER OCCUPIED ROOMS AND |
| SPACES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |