Plan Review Notes
Plan Review Notes For Permit 19020031
Permit Number 19020031
Review Stop E
Sequence Number 2
Notes
Date Text
2019-04-02 16:58:57PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
  
 NOTHING IN A COMMERCIAL CALCULATION HAS 10,000 AT 100%
 AND REMAINDER AT 40% THAT IS A RESIDENTIAL CALCULATION