Plan Review Notes
Plan Review Notes For Permit 19020031
Permit Number 19020031
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-01 11:14:401ST REVIEW: 19020031
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 2. PROVIDE WATER ISOMETRIC. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. SHOW LOCATION OF WATER HEATER ON PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 4. BAR SINK MISSING FROM SANITARY ISOMETRIC PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 5. PLEASE INDICATE ON PLAN THE KITCHEN SHALL COMPLY
 WITH FBC ACC 804
  
 6. A GREASE TRAP IS REQUIRED ON THE KITCHEN SINK. PER
 FBC PL 1003.3.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  