2019-03-01 11:14:40 | 1ST REVIEW: 19020031 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5 |
| |
| 2. PROVIDE WATER ISOMETRIC. PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) |
| |
| 3. SHOW LOCATION OF WATER HEATER ON PLAN. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 4. BAR SINK MISSING FROM SANITARY ISOMETRIC PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| 5. PLEASE INDICATE ON PLAN THE KITCHEN SHALL COMPLY |
| WITH FBC ACC 804 |
| |
| 6. A GREASE TRAP IS REQUIRED ON THE KITCHEN SINK. PER |
| FBC PL 1003.3.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |