2019-03-01 12:57:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020031
 3/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100: PLEASE PROVIDE A SCOPE OF WORK OUTLINE
 ON THE PLAN- SECTION 107.2.1 WPB.
  
 2) M100: BASED ON THE ARCHITECTURAL PLANS, THE PROPOSED
 PROJECT APPEARS TO BE A CHANGE OF OCCUPANCY, OR A LEVEL
 III ALTERATION AS INDICATED ON LS100. REFER TO SECTION
 809.2 FBC-17 EXISTING BUILDING CODE AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR.
  
 3) M100: THE PLAN APPEARS TO SHOW A NEW 5-TON AC SYSTEM
 WITH THE AIR HANDLER BEING INSTALLED IN THE ATTIC.
 PLEASE SEE SECTION C403.2.9.6 FBC EC WHICH PROHIBITS
 INSTALLATION OF AIR HANDLERS IN ATTICS.
  
 3) M100: A DUCT SMOKE DETECTORS IS REQUIRED IN THE
 SUPPLY AIR SYSTEMS OF THE NEW 5-TON AC SYSTEM PER
 SECTION 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE
 APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE
 THE SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS
 OF SUPPLY AIR.
  
 4) M100: PROVIDE THE DIMENSIONS OF THE RETURN GRILLS IN
 THE OFFICES- SECTION 603 FBC M.
  
 5) M100: PROVIDE AIR DEVICE AND AIR DISTRIBUTION
 SCHEDULES THAT INDICATE THE MAKES AND MODELS OF THE
 DIFFUSERS AND GRILLS, AND TYPE OF DUCTWORK TO BE
 INSTALLED- SECTION 603.
  
 6) M100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FLOOR GRILLS IN COMPLIANCE WITH SECTION 603.18.1 FBC M.
 THE SPECS MUST INDICATE THE GRILLS SHALL RESIST
 STRUCTURAL FAILURE AS OUTLINED IN THE SECTION.
  
 7) M100: PROVIDE A BATH AND TOILET ROOM EXHAUST FAN
 SCHEDULE, AND SHOW THE EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS- TABLE 403.3.1.1 FBC M.
  
 8) M100: PROVIDE EQUIPMENT SCHEDULES AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR ANY COOKING
 APPLIANCES TO BE INSTALLED IN THE KITCHEN AND BAR-
 SECTION 917 FBC M. PLEASE IDENTIFY THE LOCATIONS OF THE
 APPLIANCES ON THE PLAN AND PRPOVIDE LOCAL EXHAUST
 SYSTEMS (HOODS) WHERE REQUIRED. PLEASE NOTE THAT
 SEPARATE PERMITS ARE REUIRED FOR GREASE EXHAUST
 SYSTEMS- SECTION 107.2.1 WPB.
  
 9) M100: EXHAUST VENTILATION IS REQUIRED FOR THE
 KITCHEN AT A RATE OF 25 CFMS CONTINUOUSLY OR 100 CFMS
 INTERMITTENTLY IN ACCORDANCE WITH TABLE 403.3.1.1 FBC
 M. PLEASE NOTE FOOTNOTE B PROHIBITS RECIRCULATION OF
 AIR FROM THE KITCHEN TO OTHER OCCUPIED ROOMS AND
 SPACES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  