2019-02-19 11:22:09 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19020031 |
| ADD: 3020 S DIXIE/ AKA: 339 WESTMINSTER PL. |
| CONT: TIM GIVENS BUILDING & REMODELING |
| TEL: 561-533-5828 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. FEB. 19/ 2019 |
| ACTION: DENIED |
| |
| 1) WORK COMPLETED WITHOUT THE BENEFIT OF PERMITS. THE |
| SHEET A100 SHOWS THE FRONT ENTRY SET OF DOORS AS A PAIR |
| OF INSWING DOORS. THE CHANGE OF OCCUPANCY PERMIT |
| 10070543 SHOWS THESE DOORS AS OUTSWING DOORS. THERE WAS |
| ALSO A MISC. PERMIT FILED UNDER THE ADDRESS OF 339 |
| WESTMINSTER PL. PERMIT NUMBER 08040046, NOA 07-0522.05 |
| HARMAN WINDOWS AND DOORS FOR OUTSWING GLAZED WOOD |
| FRENCH DOORS, L. M. IMPACT TESTED. PLEASE PROVIDE THE |
| PRODUCT TESTING FOR THESE DOORS FOR INSWING USE. |
| |
| 2017 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION |
| OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL |
| NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL |
| STRENGTH, FIRE SAFETY, OR MEANS OF EGRESS. |
| |
| 2) THE LIFE SAFETY SHEET LS100 UNDER THE HEADING OF |
| CONSTRUCTION TYPE LIST THE CONSTRUCTION TYPE AS TYPE 5 |
| UNSPRINKLERED. PLEASE IDENTIFY IF THE TERM TYPE V |
| CONSTRUCTION IS THE TERM USED BEFORE AND IN THE 2001 |
| FBC WHERE WE HAD TYPE VI CONSTRUCTION OR ARE YOU USING |
| THE TERM SINCE IN THE 2004 FBC WHERE THE STRUCTURE IS |
| LISTED V-A 1 HOUR PROTECTED OR V-B UNPROTECTED. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) PLEASE NOTE THAT THE LIFE SAFETY PLAN LS100 SHOWS 3 |
| EXITS FROM THE BUILDING. ONLY ONE MEANS OF EGRESS IS |
| REQUIRED, SINCE THE FRONT ENTRY TO THE FURTHEST POINT |
| IN THE BUILDING OFFICE 102 OR THE KITCHEN IS UNDER 50 |
| FEET. IN THE 2017 FBC-B TABLE 1006.2.1 COMMON PATH OF |
| TRAVEL FOR A BUSINESS OCCUPANCY/ UNSPRINKLERED/ AND AN |
| OCCUPANT LOAD OF <49 THE COMMON PATH OF TRAVEL IS 75 |
| FEET. |
| SIGNAGE WILL BE REQUIRED AT THE EXITS THAT ARE NOT |
| ACCESSIBLE TO WHERE THE ACCESSIBLE EXIT IS LOCATED. |
| |
| 2017 FBC-ACCESSIBILITY CODE SECTIONS: 216.4 MEANS OF |
| EGRESS. SIGNS FOR MEANS OF EGRESS SHALL COMPLY WITH |
| 216.4. 216.4.1 EXIT DOORS. DOORS AT EXIT PASSAGEWAYS, |
| EXIT DISCHARGE, AND EXIT STAIRWAYS SHALL BE IDENTIFIED |
| BY TACTILE SIGNS COMPLYING WITH 703.1, 703.2, AND |
| 703.5. |
| 216.6 ENTRANCES. |
| |
| WHERE NOT ALL ENTRANCES COMPLY WITH 404, ENTRANCES |
| COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE |
| INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH |
| 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT |
| INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING |
| WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT |
| COMPLY WITH 404. |
| |
| 4) SHEET D100 INDICATES WITH NOTES 13 & 14 THE REMOVAL |
| OF THE CHIMNEY, ROOF TILE, PLYWOOD AND ROTTEN WOOD |
| TRUSSES, REPLACE AS NECESSARY. PLEASE NOTE COMPLIANCE |
| WITH THE 2017 FBC-EXISTING BUILDING CODE SECTION |
| 706.1.1. NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF |
| AREA OR ROOF SECTION OF ANY EXISTING BUILDING OR |
| STRUCTURE SHALL BE REPAIRED, REPLACED OR RECOVERED IN |
| ANY 12-MONTH PERIOD UNLESS THE ENTIRE EXISTING ROOFING |
| SYSTEM OR ROOF SECTION IS REPLACED TO CONFORM TO |
| REQUIREMENTS OF THIS CODE. |
| |
| 5A) SHEET D100 INDICATES UNDER THE EXISTING BUILDING |
| CODE A LEVEL 2 ALTERATION IS BEING DECLARED. PLEASE |
| REVIEW THE CLASSIFICATION OF WORK FOR A LEVEL 3 |
| ALTERATION, IT WOULD APPEAR THAT YOU HAVE MET THAT |
| THRESHOLD. EXISTING BUILDING CODE 505.2 APPLICATION. |
| LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF |
| CHAPTERS 7 AND 8 FOR LEVEL 1 AND 2 ALTERATIONS, |
| RESPECTIVELY, AS WELL AS THE PROVISIONS OF CHAPTER 9. |
| |
| 5B) PLEASE SHOW COMPLIANCE WITH THE EXISTING BUILDING |
| CODE SECTION 907.4.2 SUBSTANTIAL STRUCTURAL ALTERATION. |
| WHERE MORE THAN 30 PERCENT OF THE TOTAL FLOOR AND ROOF |
| AREAS OF THE BUILDING OR STRUCTURE HAVE BEEN OR ARE |
| PROPOSED TO BE INVOLVED IN STRUCTURAL ALTERATION WITHIN |
| A 5-YEAR PERIOD, THE EVALUATION AND ANALYSIS SHALL |
| DEMONSTRATE THAT THE LATERAL LOAD-RESISTING SYSTEM OF |
| THE ALTERED BUILDING OR STRUCTURE COMPLIES WITH THE |
| FLORIDA BUILDING CODE, BUILDING FOR WIND LOADING. |
| |
| 6A) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS. |
| (B) WINDOWS & MULLIONS. |
| (C) WALL LOUVERS. |
| (D) ROOFING PRODUCTS AND ASSEMBLIES. |
| |
| 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| |
| 6C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 6D) THRESHOLDS. 2017 ACCESS. CODE 404.2.5. THRESHOLDS, |
| IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH HIGH |
| MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT |
| DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| |
| 7) SHEET A-101 THE FLOOR PLAN AND SHEET A-500 THE DOOR |
| SCHEDULE WILL NEED TO MEET THE REQUIREMENT OF THE 2017 |
| FBC-B SECTION 1010.1.1 SIZE OF DOORS. THE REQUIRED |
| CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR |
| THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM |
| CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS |
| WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE |
| OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| DEGREES. THE DOORS IDENTIFIED AS 102, 108 & 110 DO NOT |
| MEET THIS REQUIREMENT. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |