Plan Review Notes For Permit 19011359 |
Permit Number |
19011359 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-02-24 16:58:37 | 1) ) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | 2) EXISTING PLANS ON FILE WITH THE CITY SHOW THE TOTAL | | BTU ON THIS GAS SYSTEM AS 829,000 BTU'S AND THE | | SUBMITTED GAS PLAN SHOWS A TOTAL BTU LOAD OF 725,000 | | BTU'S. REVISE THE BTU LOAD ON THE SUBMITTED GAS PLAN. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|