Plan Review Notes
Plan Review Notes For Permit 19011312
Permit Number 19011312
Review Stop B
Sequence Number 2
Notes
Date Text
2019-04-16 08:19:20***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 WPB A = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE
  
 2ND REVIEW DENIED:
  
 THE ITEMS FROM THE FIRST REVIEW HAVE BEEN ADDRESSED,
 HOWEVER DURING THE 2ND REVIEW THE FOLLOWING (2) ITEMS
 HAVE BEEN FOUND THAT NEED TO BE ADDRERSSED:
  
 1. FBC B 1612.4; THE PLANS NEED TO BE REVISED TO
 INCLUDE (COASTAL A) FLOOD DESIGN CRITERIA.
  
 2. FBC B 107.3.4/WPB A 107.3.4; THE PLANS NEED TO BE
 PREPARED AND APPROVED BY THE DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE OF PROJECT (THE (1) STRUCTURAL
 ENGINEER OF RECORD). IN ADDITION TO THE SIGNING AND
 SEALING OF PLANS, THE STRUCTURAL ENGINEER OF RECORD
 NEEDS TO REVIEW (STAMP) AND SIGN
 ALL DELEGATED STRUCTURAL WORK AS WELL.
  
 NOTE: AS PER PRIOR COMMUNICATIONS WITH CHIEF PLANS
 EXAMINER (SAMANTHA HILL) FEEL FREE TO RESPOND BY EMAIL:
 [email protected] AND [email protected].