2019-05-07 14:58:00***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD REVIEW DENIED:
  
 1A. FAIL, ON SHEET 1?1, THE OCCUPANCY STILL SHOWS AS
 R?3; THE OCCUPANCY SHOULD BE R?2. (UNDER DESIGN
 CRITERIA OF PAGE 1-1 THE PLANS HAVE NOT CHANGED)
  
 1B. OK
  
 1C. OK
  
 2. OK
  
 3A. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE STRUCTURE?BORNE SOUND SPECIFICATIONS. PLEASE
 SUBMIT THE SOUND INSULATION IMPACT TEST
 SPECIFICATIONS/RESULTS FOR THE CHOSEN FLOORING
 UNDERLAYMENT AS PER ASTM E 492.
  
 3B. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE AIR?BORNE SOUND SPECIFICATIONS. PLEASE SUBMIT
 THE SOUND TRANSMISSION TEST SPECIFICATIONS/RESULTS FOR
 THE CHOSEN FLOORING UNDERLAYMENT AS PER ASTM E 90.
  
 3C. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE FLAME SPREAD SPECIFICATIONS. PLEASE SUBMIT THE
 FLAME SPREAD TEST SPECIFICATIONS/RESULTS AS PER ASTM E
 84 OR UL 723.
  
 4. OK