Plan Review Notes For Permit 19011248 |
Permit Number |
19011248 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-04-02 14:01:14 | 4/2/19 | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) THERE IS NO INDICATION OF A SMOKE ALARM IN TWO | | BEDROOMS, PER NFPA 101, A SMOKE ALARM IS REQUIRED IN | | EACH. | | | | | | NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS | | | | 31.3.4.5 SMOKE ALARMS. | | | | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED | | THROUGHOUT WITH AN | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, | | SMOKE ALARMS | | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS | | MODIFIED BY 31.3.4.5.2, | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | OF THE BEDROOMS | | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING | | BASEMENTS. | | | | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED | | THROUGHOUT WITH AN | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR | | A COMPLETE, | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | WITH 31.3.5, | | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA | | IN | | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. | | | | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE | | PERMITTED TO BE | | BATTERY POWERED. | | | | | | PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|