Plan Review Notes
Plan Review Notes For Permit 19011248
Permit Number 19011248
Review Stop B
Sequence Number 1
Notes
Date Text
2019-02-11 11:57:232017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011248
 ADD: 2400 PRESIDENTIAL WAY, SUITE: 401
 CONT: SUNSTREAM BUILDING ENTERPRISE
 TEL: 954-234-0892
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 11/ 2019
 ACTION: DENIED
  
 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST
 THE:
  
 1A) OCCUPANCY TYPE AS R-3. PLEASE NOTE UNDER THE 2017
 FBC-B SECTION 310.5 IS FOR SINGLE FAMILY DWELLINGS NOT
 FOR UNITS IN HIGHRISE BUILDINGS. SECTION 310.4 LIST
 APARTMENTS (LONG TERM NON-TRANSIENT)AND CONDOS AS R2
 UNITS, PLEASE UPDATE PLANS.
  
 1B) THIS SHEET LIST THE CONSTRUCTION TYPE AS V-B.
 PLEASE UPDATE THE PLANS, THIS BUILDING IS A HIGHRISE
 AND WILL NEED TO SHOW A CONSTRUCTION TYPE: I-A
 NON-SPRINKLERED FOOTNOTE D. 2017 FBC-B TABLE 506.2.
  
 1C) THE PLAN ALSO INDICATES AN ALTERATION LEVEL I.
 PLEASE NOTE THIS ALTERATION LEVEL IS CONSIDERED A LEVEL
 II ALTERATION. PLEASE REVIEW THE 2017 FBC-EXISTING
 BUILDING CODE SECTION 504.1 LEVEL 2 ALTERATION. LEVEL 2
 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE
 ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
 RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE
 INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
 THE RELOCATION OF THE STOVE AND DISH WASHER WOULD BE
 THE RECONFIGURATION OR EXTENSION OF A SYSTEM.
  
 2) SHEET 1-1 UNDER THE HEADING APPLICABLE CODES THE
 2017 RESIDENTIAL CODE IS STATED. PLEASE NOTE THE ONLY
 TIME THE RESIDENTIAL CODE IS USED IS IN ONE & TWO
 FAMILY DWELLINGS NOT WHEN IN HIGH-RISES.
 2017 FBC-RESIDENTIAL CODE, R101.2 SCOPE. THE PROVISIONS
 OF THE FLORIDA BUILDING CODE, RESIDENTIAL SHALL APPLY
 TO THE CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT,
 REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY,
 LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND
 TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE
 STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE
 MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE
 THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT.
  
 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST
 REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE
 FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE
 WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER