2019-02-11 11:57:23 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19011248 |
| ADD: 2400 PRESIDENTIAL WAY, SUITE: 401 |
| CONT: SUNSTREAM BUILDING ENTERPRISE |
| TEL: 954-234-0892 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. FEB. 11/ 2019 |
| ACTION: DENIED |
| |
| 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST |
| THE: |
| |
| 1A) OCCUPANCY TYPE AS R-3. PLEASE NOTE UNDER THE 2017 |
| FBC-B SECTION 310.5 IS FOR SINGLE FAMILY DWELLINGS NOT |
| FOR UNITS IN HIGHRISE BUILDINGS. SECTION 310.4 LIST |
| APARTMENTS (LONG TERM NON-TRANSIENT)AND CONDOS AS R2 |
| UNITS, PLEASE UPDATE PLANS. |
| |
| 1B) THIS SHEET LIST THE CONSTRUCTION TYPE AS V-B. |
| PLEASE UPDATE THE PLANS, THIS BUILDING IS A HIGHRISE |
| AND WILL NEED TO SHOW A CONSTRUCTION TYPE: I-A |
| NON-SPRINKLERED FOOTNOTE D. 2017 FBC-B TABLE 506.2. |
| |
| 1C) THE PLAN ALSO INDICATES AN ALTERATION LEVEL I. |
| PLEASE NOTE THIS ALTERATION LEVEL IS CONSIDERED A LEVEL |
| II ALTERATION. PLEASE REVIEW THE 2017 FBC-EXISTING |
| BUILDING CODE SECTION 504.1 LEVEL 2 ALTERATION. LEVEL 2 |
| ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE |
| ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE |
| RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE |
| INSTALLATION OF ANY ADDITIONAL EQUIPMENT. |
| THE RELOCATION OF THE STOVE AND DISH WASHER WOULD BE |
| THE RECONFIGURATION OR EXTENSION OF A SYSTEM. |
| |
| 2) SHEET 1-1 UNDER THE HEADING APPLICABLE CODES THE |
| 2017 RESIDENTIAL CODE IS STATED. PLEASE NOTE THE ONLY |
| TIME THE RESIDENTIAL CODE IS USED IS IN ONE & TWO |
| FAMILY DWELLINGS NOT WHEN IN HIGH-RISES. |
| 2017 FBC-RESIDENTIAL CODE, R101.2 SCOPE. THE PROVISIONS |
| OF THE FLORIDA BUILDING CODE, RESIDENTIAL SHALL APPLY |
| TO THE CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT, |
| REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY, |
| LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND |
| TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE |
| STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE |
| MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE |
| THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT. |
| |
| 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST |
| REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE |
| FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE |
| WITH: |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2017) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |