Plan Review Notes
Plan Review Notes For Permit 19011234
Permit Number 19011234
Review Stop THRESHOLD
Sequence Number 1
Notes
Date Text
2019-02-12 11:47:492017 FBC- BUILDING PLAN REVIEW/ THRESHOLD
 W. P. B. PERMIT: 19011234
 ADD: 625 N FLAGLER DR. / ROOFTOP REPLACEMENT OF STEEL &
 MECHANICAL EQUIPMENT
 CONT: RPM&M GENERAL CONTRACTORS, INC.
 TEL: 954-649-5304
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 12/ 2019
 ACTION: DENIED
  
 1) PLEASE NOTE THE WORK TO BE COMPLETED UNDER THIS
 PERMIT, THE BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) MISSING. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) SEMI-COMPLIED. SUBMITTED THRESHOLD / SPECIAL
 INSPECTOR AGREEMENT. ONLY ONE OF THE JOBSITE INSPECTORS
 QUALIFIES CHARLES MOCK. THE VIRGINIA EIT SHUBHAM
 PUTTABOREGOWDA IS ELIGIBLE FOR THE EXAM BUT TO DATE HAS
 NOT PASSED THE EXAM. HE HAS BEEN STRUCK AND NOT
 ELIGIBLE UNDER FLORIDA STATUTE 553.79(5) AND THE 2017
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION:
 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM STRUCTURAL INSPECTION
 OF THRESHOLD BUILDINGS REQUIRED BY THIS CODE, SECTION
 553.73, FLORIDA STATUTES, WITHOUT DUPLICATIVE
 INSPECTION BY THE BUILDING DEPARTMENT. THE BUILDING
 OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON
 CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR UNDER
 CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS OF
 THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5),
 FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE.
 1C) THE STRUCTURAL PLANS WILL ALSO NEED TO SUPPLY A
 STRUCTURAL INSPECTION PLAN AND MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 2017 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION:
 110.8.1.
  
 1D) PLEASE SHOW COMPLIANCE WITH 2017 CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION SECTION:
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633. FLORIDA STATUTES.
  
 1E) PLEASE NOTE ONLY 2 SETS OF PLANS WERE SUBMITTED.
 NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED,
 (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.7 THRESHOLD BUILDINGS, GUIDELINES AND POLICIES
 FOR PROJECTS CONCERNING SPECIAL INSPECTORS.
  
 1F) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  