Notes |
Date |
Text |
2019-02-26 09:46:53 | APPROVED | | PROVISO | | 1. A PLUMBING PERMIT IS REQUIRED | | 2. A SEPARATE PERMIT IS REQUIRED FOR THE NEW BACKFLOW | | PREVENTOR (SEE M-300 P&ID) PROVIDED FOR MAKE UP WATER | | FOR NEW CHILLED WATER SYSTEM. PROVIDE CERTIFICATION | | DOCUMENTS AT FINAL INSPECTION. | | 3. REGARDING EXISTING BACKFLOW PREVENTER FOR MAKE UP | | WATER TO THE COOLING TOWERS (SEE M-201 PHOTO; EXISTING | | CONDITIONS), PROVIDE CURRENT CERTIFICATION DOCUMENTS | | PROVIDED WITHIN THE PREVIOUS TWO YEARS OR NEW DOCUMENTS | | AT FINAL INSPECTION. | | 4. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S | | APPROVAL |
|