2019-02-25 17:23:18 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19011234 |
| 2/25/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) COMMISSIONING OF THE NEW HVAC SYSTEMS IS REQUIRED |
| PER SECTION C408.2 FBC-17 ENERGY CONSERVATION. SUBMIT A |
| COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND |
| DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE |
| THAT A COPY OF THE COMMISSIONING REPORT SHALL BE |
| SUBMITTED FOR REVIEW AT FINAL INSPECTION. |
| |
| 2) SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE |
| DETECTORS IN THE SUPPLY AIR SYSTEMS OF THE NEW AIR |
| HANDLERS- SECTION 606.2.1 FBC M |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |