Plan Review Notes
Plan Review Notes For Permit 19011226
Permit Number 19011226
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-12 10:47:52PLUMBING 1ST REVIEW***DENIED
  
 1) SHT P.01 SHOW 5 KITCHEN SINKS @ 2 DFU'S EACH PER FBC
 P 7091. GIVEN A TOTAL OF 10 DFU'S IS NOT PERMITTED ON
 2" HORIZONTAL DRAIN. MAX IS 6 DFU'S PER FBC P 710.1
 (2). WILL NEED TO CHANGE TO 3"
  
 2) SHT P.01 NOTES # 11 AND 25 REFER TO THE CODE IN
 AFFECT AS THE 5TH EDTION. THE 2017 IS THE 6TH EDTION
 AND THE CURRENT CODE IN AFFTECT. PLEASE ADDRESS
  
 3) PLEASE PROVIDE ON THE PLAN THE APPROACH AND THE
 CLEAR FLOOR SPACE AT EACH SINK COMPLYING WITH FBC
 ACCESSIBILITY 212 AND 305
  
  