Plan Review Notes For Permit 19011225 |
Permit Number |
19011225 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-12 11:01:44 | PLUMBING 1ST REVIEW***DENIED | | | | 1) SHT P.01 SHOW 5 KITCHEN SINKS @ 2 DFU'S EACH PER FBC | | P 7091. GIVEN A TOTAL OF 10 DFU'S IS NOT PERMITTED ON | | 2" HORIZONTAL DRAIN. MAX IS 6 DFU'S PER FBC P 710.1 | | (2). WILL NEED TO CHANGE TO 3" | | | | 2) SHT P.01 NOTES # 11 AND 25 REFER TO THE CODE IN | | AFFECT AS THE 5TH EDTION. THE 2017 IS THE 6TH EDTION | | AND THE CURRENT CODE IN AFFTECT. PLEASE ADDRESS | | | | 3) PLEASE PROVIDE ON THE PLAN THE APPROACH AND THE | | CLEAR FLOOR SPACE AT EACH SINK COMPLYING WITH FBC | | ACCESSIBILITY 212 AND 305 | | | | | | TIM HUNT | | PLUMBING PLAN EXAMINER/ PLUMBING INSPECTOR | | 561-248-2073 | | | | SAMANTHA HILL | | CHIEF PLAN EXAMINER | | 561-805-6724 | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 |
|