Plan Review Notes
Plan Review Notes For Permit 19011159
Permit Number 19011159
Review Stop G
Sequence Number 1
Notes
Date Text
2019-04-23 11:17:12GAS 1ST REVIEW**DENIED**04/23/2019
  
 1) PLAN THAT BEAR THE DESIGN PROFESSIONAL NAME,
 LICENSE, AND OR TITLE BLOCK ARE REQUIRED TO BE WET
 SIGN. NONE OF THE PAGES SUBMITTED ARE SIGNED. FAC
 61G15-23.001
  
 2) PROVIDE MAKE UP AIR CALCULATION FOR THE KITCHEN
 STOVE. FBC 107.3.5. FBCG 403.9.3
  
 3) PROVIDE LOCATION OF SHUT OFF VALVE THAT WILL ALLOW
 READY ACEESS. HAVING TO REMOVE THE STOVE UNDER
 DEFINITION IS NOT HAVING READY ACCESS. FBC 107.2.1
  
 4) SHT G-1 ON PLAN KEY NOTES #2 REFERS TO SHT P-1 FOR
 WATER HEATER SPECIFICATIONS. NO SHT P-1 WAS SUBMITTED.
 SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  