Plan Review Notes
Plan Review Notes For Permit 19011155
Permit Number 19011155
Review Stop B
Sequence Number 1
Notes
Date Text
2019-02-26 12:42:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011155
 ADD: 250 S AUSTRALIAN AVE. 17TH & 18TH FLOORS
 CONT: TURNER CONSTRUCTION
 TEL: 786-9000
 E-MAIL: [email protected] NUNEZ DARA
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 26TH/ 2019
 ACTION: DENIED
  
 1) SHEET 003_A102 PARTITION TYPES. WALL TYPE 1/ TYPE R
 IS INDICATED AS A ONE HOUR FR WALL. IF THIS WALL TYPE
 IS A ONE HOUR FIRE PARTITION PLEASE PROVIDE COMPLIANCE
 WITH 2017 FBC-B 708.3 FIRE-RESISTANCE RATING, PLEASE
 PROVIDE AN ASSEMBLY NUMBER (UL OR GYPSUM ASSOCIATION)
 SHOWING THE COMPONENTS OF THE WALL, SPACING OF STUDS
 AND THE HEIGHT LIMITATIONS.
  
 2) SHEET 003_A102 PARTITION TYPES. WALL TYPES 1 & 2
 INDICATE THE BOTTOM PLATE IS TO BE SHOOT INTO THE SLAB
 USING HILTI PINS, HOW LONG ARE THE PINS AND WHAT TYPE
 OF FLOOR SLAB DOES THIS BUILDING HAVE, POST TENSION
 TENDONS? WALL TYPE DETAILS 3 & 4 ALSO INDICATE THE USE
 OF POWER ACTIVATED PINS ? INCH DIA. X 1 ? INCHES LONG.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET 003_A102 PARTITION TYPES 3 & 4 BOTH SHOW 6
 INCH CONCRETE STEEL TUBES BEING CORED INTO THE FLOOR
 SLAB. THERE IS AGAIN NO NOTATION AS TO CAUTION OF THE
 TYPE OF FLOOR SLAB, IF TENDONS COULD BE CUT, THE WIDTH
 OF THE WHOLE, THE DEPTH OF THE HOLE, NOR HOW THICK THE
 SLAB REALLY IS. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) SHEET 003_A102 THE TOP OF THE PARTITIONS THERE IS NO
 MENTION AS TO HOW TO SECURE THE WALL SYSTEMS WITH
 EXCEPTION TO WALL TYPE 3 THAT SHOWS WHAT MIGHT BE A
 LINEAR DIFFUSER BEING ANCHORED IN TO THE FLOOR ABOVE
 NOTE INDICATES APPROVED METAL INSERT OR ANCHOR, PLEASE
 PROVIDE THE TYPE OF ANCHOR.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 5) SHEET 005_A200.1 CONSTRUCTION PLANS. THIS FLOOR PLAN
 DOES NOT INDICATE WHAT WALLS ARE NEW AND WHAT WALLS
 REMAINED. THERE ARE VERY FEW MEASUREMENTS TO EVEN
 REVIEW FOR CODE COMPLIANCE, THE STAIRWAY WALLS,
 ELEVATOR WALLS ARE NOT EVEN IN THE WALL TYPE LEGEND
 FOUND ON THIS PAGE. PLEASE NOTE THE DOORS THAT MAKE UP
 THE ELEVATOR LOBBY ARE ON WALLS BUILT OUT FROM THE 2
 HOUR SHAFT ENCLOSURES FOR THE ELEVATORS BUT THERE IS NO
 MENTION OF THE WALL TYPE, PLEASE NOTE THE ELEVATOR
 LOBBY WALLS ONLY NEED TO BE A 1 HOUR SEE FBC-B TABLE
 716.5 FOR WALL TYPES AND RATINGS AS WELL AS OPENING
 PROTECTIVES.
  
 6) SHEET 005_A200.1 CONSTRUCTION PLANS & 006_A200.2.
 BOTH SHEETS INDICATE A COMMUNICATING STAIR BETWEEN 2
 STORIES WITH NO ENCLOSURE, IS THIS A NEW OPENING, DOES
 THIS STAIR GO FURTHER THAN THE 2 STORIES WHERE WORK IS
 TO OCCUR? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 SHOW HOW COMPLIANCE WITH THE 2017 FBC-B SECTION 1019.3.
  
  
 7) SHEET 005_A200.1 CONSTRUCTION PLANS & 006_A200.2.
 PLEASE SHOW ON BOTH FLOOR PLAN COMMON PATH OF TRAVEL
 AND THE TRAVEL DISTANCES EXCEEDS THE VALUES LISTED IN
 TABLE 1006.2.1 OR WHERE THE DESIGN OCCUPANT LOAD
 EXCEEDS THAT FOUND IN TABLE 1006.2.12.
  
 8) SHEET 005_A200.1 CONSTRUCTION PLANS & 006_A200.2.
 BOTH SHEETS INDICATE THE USE OF MICROWAVES INSTALLED IN
 THE UPPER CABINETS, PLEASE SHOW HOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE WILL OCCUR:
 8A) 308 REACH RANGES. 308.2 FORWARD REACH / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 8B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 9) SHEET 013_A500 THE RESTROOM ELEVATIONS 4 & 5 DO NOT
 SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 SECTIONS:
 604.5 GRAB BARS.
 9A) 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR SHALL BE
 42 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE
 REAR WALL.
  
 9B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE
 36 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE
 OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 9C) PLEASE ALSO SEE DETAILS 4 & 5 AS TO WHERE YOU
 MEASURE FOR HEIGHT, TO THE TOP OF THE GRIPPING SURFACE
 NOT CENTER-LINE. SEE RESTROOM NOTE # 2.
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  