Plan Review Notes For Permit 19011071 |
Permit Number |
19011071 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-02-12 06:01:28 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE SOUNDPROOFING UNDERLAYMENT FOR | | THE TILE FLOOR. | | STRUCTURE-BORNE SOUND - THE UNDERLAYMENT SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 OR NOT LESS THAN 45 IF FIELD TESTED,WHEN TESTED IN | | ACCORDANCE WITH ASTM E492. 2017 FBC-BUILDING | | SEC.1207.3. | | 2) AIR-BORNE SOUND - FLOOR /CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS AND SLEEPING UNITS SHALL HAVE A SOUND | | TRANSMISSION CLASS (STC) OF NOT LESS THAN 50,OR NOT | | LESS THAN 45 IF FIELD TESTED FOR AIR-BORNE NOISE WHEN | | TESTED IN ACCORDANCE WITH ASTM E90. 2017 FBC-BUUILDING | | SEC. 1207.2. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|