Date |
Text |
2019-06-12 10:05:03 | PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH |
| RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| 1) VALUE STILL APPEARS TOO LOW. PROVIDE ACTUAL SIGNED |
| CONTRACTS NOT EMAILS OF EST. THE PLUMBING FIXTURES, ADA |
| LIFT AND DESIGN COST HAVE NOT BEEN INCLUDED IN YOUR |
| VALUATION SUBMITTAL. WPB AMEND 109.3 |
| |
| 2) PLANS SUBMITTED ARE NOT SIGNED AND SEALED BY DESIGN |
| PROFESSIONAL. THE EXISTING FLOOR PLAN LAY OUT HAS BEEN |
| REMOVED.F.S 471, 481 |
| |
| 3) TANKLESS WATER HEATER INSTALLATION MANUAL CALLS OUT |
| ONLY A 10F HEAT RISE PRODUCING A MAX 90F OF HOT WATER @ |
| 2GPM. PER FBC-P 607.1 HOT WATER SHALL BE REQUIRED. HOT |
| WATER IS DEFINED AS 110F OR GREATER. SUBMIT A TANKLESS |
| WATER HEATER WITH A MIN OF 30F HEAT RISE @ 2GPM. FBC-P |
| 604.3. PLEASE NOTE BY CHANGING THE KW OF THE HWH THE |
| ELC DEMAND AND WIRE SIZE WILL INCREASE. PLEASE BE SURE |
| TO REVISE THE ELC LOAD AND PLAN ACCORDINGLY. |
| |
| 4) PROVIDE CLEAR FLOOR SPACE, TUNING SPACE, AND |
| ACCESSIBLE ROUTE OF AND TO THE BREAK ROOM SINK. ALL |
| ELEMENTS SHALL MEET FLORIDA ACCESSIBILITY. 606.2, 305, |
| 402, 403 |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| CITY OF WEST PALM BEACH |
| 561-248-2703 |
| [email protected] |
| [email protected] |
| |