2019-05-16 08:13:10 | PLUMBING 2ND REVIEW**DENIED** |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| |
| 1) THE VALUE SEEMS LOW. THIS WAS ADDRESSED BY THE |
| ELECTRICAL PLANS REVIEWER ON THE 1ST REVIEW BUT NO |
| DOCUMENTATION WAS SUBMITTED TO ADDRESS THIS COMMENT. |
| 2ND REQUEST:PROVIDE A SIGNED BONA FIDE CONTRACT TO |
| INCLUDE THE ENTIRE SCOPE OF WORK FOR THIS PROJECT. FL |
| ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF DESIGN |
| PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS |
| IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| REVIEW. |
| |
| 2) PROVIDE THE LOCATION OF DISCHARGE THAT THE LIFT |
| STATION SHALL PUMP TO. PROVIDE CHECK VALVE AND MATERIAL |
| TO BE USED. FBC 107.2. |
| |
| 3) PROVIDE THE INSTALLATION MANUAL FOR THE LIFT |
| STATION. FBC 107.2.1 |
| |
| 4) PROVIDE THE INSTALLATION MANUAL FOR THE TANKLESS |
| WATER HEATER TO INCLUDE THE HEAT RISE CHART SHOWING THE |
| HEATER IS CAPABLE OF PRODUCING HOT WATER MIN 110F TO |
| THE FIXTURE AS REQUIRED FBC P 607.1. |
| |
| 5) YOU ISOMETRIC APPEARS TO SHOW THE USE OF AAV'S. A |
| VENT SHALL BE REQUIRED AS TO NOT ALLOW THE LIFT PUMP TO |
| BECOME AIR BOUND AND AS A SEPARATE BUILDING DRAIN VENT |
| SHALL EXTENT TO THE OUT DOORS. FBC 901.2.1, 904.1 |
| |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| BUILDING DIVISION |
| CITY OF WEST PALM BEACH |
| 401 CLEMATIS STREET, 1ST FLOOR |
| WEST PALM BEACH, FL 33401 |
| 561-248-2703 |
| [email protected] |
| [email protected] |