Plan Review Notes
Plan Review Notes For Permit 19011061
Permit Number 19011061
Review Stop P
Sequence Number 2
Notes
Date Text
2019-05-16 08:13:10PLUMBING 2ND REVIEW**DENIED**
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 1) THE VALUE SEEMS LOW. THIS WAS ADDRESSED BY THE
 ELECTRICAL PLANS REVIEWER ON THE 1ST REVIEW BUT NO
 DOCUMENTATION WAS SUBMITTED TO ADDRESS THIS COMMENT.
 2ND REQUEST:PROVIDE A SIGNED BONA FIDE CONTRACT TO
 INCLUDE THE ENTIRE SCOPE OF WORK FOR THIS PROJECT. FL
 ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
 2) PROVIDE THE LOCATION OF DISCHARGE THAT THE LIFT
 STATION SHALL PUMP TO. PROVIDE CHECK VALVE AND MATERIAL
 TO BE USED. FBC 107.2.
  
 3) PROVIDE THE INSTALLATION MANUAL FOR THE LIFT
 STATION. FBC 107.2.1
  
 4) PROVIDE THE INSTALLATION MANUAL FOR THE TANKLESS
 WATER HEATER TO INCLUDE THE HEAT RISE CHART SHOWING THE
 HEATER IS CAPABLE OF PRODUCING HOT WATER MIN 110F TO
 THE FIXTURE AS REQUIRED FBC P 607.1.
  
 5) YOU ISOMETRIC APPEARS TO SHOW THE USE OF AAV'S. A
 VENT SHALL BE REQUIRED AS TO NOT ALLOW THE LIFT PUMP TO
 BECOME AIR BOUND AND AS A SEPARATE BUILDING DRAIN VENT
 SHALL EXTENT TO THE OUT DOORS. FBC 901.2.1, 904.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]